2014-09-22 15:17:37 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) PROVIDE BUCK DETAILS FOR THE OVER HEAD GARAGE DOOR, |
| EXTERIOR DOORS AND WINDOWS. FBC R612.10.2.1 |
| |
| 2) SHEET A-1 OF THE PLANS HAS WHITE-OUT IN TWO |
| LOCATIONS. SIGNED AND SEALED PLANS ARE NOT ALLOWED TO |
| BE ALTERED IN THIS MANNER. FBC 107.1, FS 471 AND FS 481 |
| |
| 3) PROVIDE A ROOF FRAMING PLAN THAT SPECIFIES THE |
| ANCHORS/UPLIFT (ROOF TO WALL CONNECTIONS) FOR THE NEW |
| ROOF TRUSSES AND GIRDERS. FBC 107.3.5.3 |
| |
| 4) THE TRUSS PLANS SPECIFY A 24" WOOD GIRDER THAT HAS |
| THREE POINT BEARING. THE ARCHITECTURAL PLANS SHOW ONE |
| END OF THIS GIRDER BEARING ON AN EXTERIOR WALL ABOVE |
| THE KITCHEN WINDOWS. THE INTERMEDIATE BEARING POINT IS |
| NOT IDENTIFIED AND THE OTHER END APPEARS TO BE WHERE |
| THE TRUSS LAYOUT PLAN HAS THE MID-POINT BEARING. |
| PROVIDE STRUCTURAL DETAILS AND SECTIONS OF THE BEARING |
| WALLS THAT SUPPORT THIS GIRDER TRUSS. SHOW IN DETAIL |
| HOW THE LOADS WILL BE SAFELY SUPPORTED AND TRANSFERED |
| FROM THE ROOF TO THE FOUNDATION. FBC R301.1 |
| |
| 5) THE TRUSS LAYOUT AND DRAWINGS FROM THE DELEGATED |
| ENGINEER ARE REQUIRED TO BE REVIEWED AND APPROVED BY |
| THE DESIGNER OF RECORD. A SHOP DRAWING REVIEW STAMP |
| APPROVING THE TRUSS LAYOUT AND DESIGN FROM THE DESIGNER |
| OF RECORD IS REQUIRED ON THE TRUSS LAYOUT. FAC |
| 61G15-30.005 & 61G15-31.003 |
| |
| 6) THE DIMENSIONS ON THE PLANS INDICATE THAT IT IS 33' |
| FROM THE OUTSIDE OF THE WALLS SUPPORTING THE LONGER |
| TRUSSES WHICH ARE SPECIFIED AS 32' 9" LONG (NOT |
| INCLUDING THE OVERHANG). THE DIMENSIONS FOR THE OTHER |
| AREA THAT IS RECEIVING THE NEW TRUSSES ARE NOT |
| INDICATED ON THE PLANS. |
| |
| 7) THE INTERIOR BEARING WALL BETWEEN THE BATHROOM AND |
| BEDROOM IS NOT SPECIFIED AS SUCH ON THE PLANS. THIS |
| SECTION OF WALL WAS NOT A BEARING WALL. PROVIDE DETAILS |
| TO SHOW HOW IT WILL BE CONVERTED TO A BEARING WALL. FBC |
| 107.2.1.3 |
| |
| 8) THE COLUMN DETAIL ON SHEET A-1 IS MISSING |
| INFORMATION, SUCH AS, THE POST SIZE AND WALL THICKNESS, |
| THE WELD TYPES AT END PLATES, THE LENGTH / EMBED DEPTH |
| OF THE ANCHOR AND LAG BOLTS. ALSO, IT IS NOT CLEAR ON |
| THE PLANS WHAT THIS COLUMN IS SUPPORTING. FBC 107.2.1 & |
| 107.2.1.3 |
| |
| 9) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| POLYFOAM ROOF TILE ADHESIVE AS REQUIRED BY DCA RULE |
| 9N-3. |
| |
| 10) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| AMENDMENTS 107.3.4.1 |
| |
| 11) SUBMIT CALCULATIONS FOR INDOOR COMBUSTION AIR FOR |
| THE TANK-LESS GAS WATER HEATER LOCATED IN THE UTILITY |
| CLOSET. FBCR G2407 (304) THIS COMMENT NEEDS TO BE |
| ADDRESSED BEFORE THIS PERMIT IS ISSUED. THE MECHANICAL |
| PLANS CALL FOR A LOUVERED DOOR TO THIS ROOM AND THE |
| DOOR SCHEDULE ON THE ARCHITECTURAL PLANS SPECIFY A |
| SOLID DOOR. SEE MECHANICAL COMMENTS. |
| |
| 12) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE |
| SIGNED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION |
| 405.4.2 |
| |
| IN ORDER TO HELP SPEED THE REVIEW PROCESS, PLEASE |
| SUBMIT A RESPONSE LETTER THAT INDICATES HOW EACH OF THE |
| REVIEW COMMENTS WAS ADDRESSED. |
| |