Plan Review Notes
Plan Review Notes For Permit 14060052
Permit Number 14060052
Review Stop B
Sequence Number 2
Notes
Date Text
2014-09-22 15:17:372010 FBC
  
 DENIED BY BUILDING
  
 1) PROVIDE BUCK DETAILS FOR THE OVER HEAD GARAGE DOOR,
 EXTERIOR DOORS AND WINDOWS. FBC R612.10.2.1
  
 2) SHEET A-1 OF THE PLANS HAS WHITE-OUT IN TWO
 LOCATIONS. SIGNED AND SEALED PLANS ARE NOT ALLOWED TO
 BE ALTERED IN THIS MANNER. FBC 107.1, FS 471 AND FS 481
  
 3) PROVIDE A ROOF FRAMING PLAN THAT SPECIFIES THE
 ANCHORS/UPLIFT (ROOF TO WALL CONNECTIONS) FOR THE NEW
 ROOF TRUSSES AND GIRDERS. FBC 107.3.5.3
  
 4) THE TRUSS PLANS SPECIFY A 24" WOOD GIRDER THAT HAS
 THREE POINT BEARING. THE ARCHITECTURAL PLANS SHOW ONE
 END OF THIS GIRDER BEARING ON AN EXTERIOR WALL ABOVE
 THE KITCHEN WINDOWS. THE INTERMEDIATE BEARING POINT IS
 NOT IDENTIFIED AND THE OTHER END APPEARS TO BE WHERE
 THE TRUSS LAYOUT PLAN HAS THE MID-POINT BEARING.
 PROVIDE STRUCTURAL DETAILS AND SECTIONS OF THE BEARING
 WALLS THAT SUPPORT THIS GIRDER TRUSS. SHOW IN DETAIL
 HOW THE LOADS WILL BE SAFELY SUPPORTED AND TRANSFERED
 FROM THE ROOF TO THE FOUNDATION. FBC R301.1
  
 5) THE TRUSS LAYOUT AND DRAWINGS FROM THE DELEGATED
 ENGINEER ARE REQUIRED TO BE REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD. A SHOP DRAWING REVIEW STAMP
 APPROVING THE TRUSS LAYOUT AND DESIGN FROM THE DESIGNER
 OF RECORD IS REQUIRED ON THE TRUSS LAYOUT. FAC
 61G15-30.005 & 61G15-31.003
  
 6) THE DIMENSIONS ON THE PLANS INDICATE THAT IT IS 33'
 FROM THE OUTSIDE OF THE WALLS SUPPORTING THE LONGER
 TRUSSES WHICH ARE SPECIFIED AS 32' 9" LONG (NOT
 INCLUDING THE OVERHANG). THE DIMENSIONS FOR THE OTHER
 AREA THAT IS RECEIVING THE NEW TRUSSES ARE NOT
 INDICATED ON THE PLANS.
  
 7) THE INTERIOR BEARING WALL BETWEEN THE BATHROOM AND
 BEDROOM IS NOT SPECIFIED AS SUCH ON THE PLANS. THIS
 SECTION OF WALL WAS NOT A BEARING WALL. PROVIDE DETAILS
 TO SHOW HOW IT WILL BE CONVERTED TO A BEARING WALL. FBC
 107.2.1.3
  
 8) THE COLUMN DETAIL ON SHEET A-1 IS MISSING
 INFORMATION, SUCH AS, THE POST SIZE AND WALL THICKNESS,
 THE WELD TYPES AT END PLATES, THE LENGTH / EMBED DEPTH
 OF THE ANCHOR AND LAG BOLTS. ALSO, IT IS NOT CLEAR ON
 THE PLANS WHAT THIS COLUMN IS SUPPORTING. FBC 107.2.1 &
 107.2.1.3
  
 9) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 POLYFOAM ROOF TILE ADHESIVE AS REQUIRED BY DCA RULE
 9N-3.
  
 10) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 11) SUBMIT CALCULATIONS FOR INDOOR COMBUSTION AIR FOR
 THE TANK-LESS GAS WATER HEATER LOCATED IN THE UTILITY
 CLOSET. FBCR G2407 (304) THIS COMMENT NEEDS TO BE
 ADDRESSED BEFORE THIS PERMIT IS ISSUED. THE MECHANICAL
 PLANS CALL FOR A LOUVERED DOOR TO THIS ROOM AND THE
 DOOR SCHEDULE ON THE ARCHITECTURAL PLANS SPECIFY A
 SOLID DOOR. SEE MECHANICAL COMMENTS.
  
 12) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE
 SIGNED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION
 405.4.2
  
 IN ORDER TO HELP SPEED THE REVIEW PROCESS, PLEASE
 SUBMIT A RESPONSE LETTER THAT INDICATES HOW EACH OF THE
 REVIEW COMMENTS WAS ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]