Plan Review Notes
Plan Review Notes For Permit 14060052
Permit Number 14060052
Review Stop P
Sequence Number 1
Notes
Date Text
2014-06-21 10:34:452010 FBC
  
 PLUMBING IS DENIED
  
 1) THE RISER DIAGRAM IS DRAWN INCORRECTLY AND DOES NOT
 MATCH THE PLANS. ALL OF THE FIXTURE DRAINS ( EXCEPT THE
 KITCHEN SINK ) ARE SHOWN CONNECTED TO THE VERTICAL VENT
 PIPING. FBCR P3101.2.1 SUBMIT CORRECTED DRAWINGS.
  
 2) THE EXISTING BATH DRAIN AND VENT PIPING NEEDS TO BE
 SHOWN ON THE FLOOR AND RISER PLANS. CITY AMENDMENTS
 107.1
  
 3) THE MAXIMUM DISTANCE OF THE TRAP TO THE VENT HAS
 BEEN EXCEEDED AT THE LAVATORY IN THE MASTER BATH. FBCR
 P3105.1
  