Notes |
Date |
Text |
2014-06-06 12:10:00 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | NOTICE IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME | | TRUSS-TYPE CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR | | ANY MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR | | MORE WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME | | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED | | WITH AN APPROVED SYMBOL. THE APPROVED SYMBOL SHALL BE | | PLACED WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY | | DOOR. | | | | A KNOX BOX AND KEY SYSTEM IS REQUIRED FOR THIS BUILDING | | FOR ENTRY BY FIRE PERSONNEL IN THE EVENT OF AN | | EMERGENCY AT ANY TIME. | | | | SHEET M1 DOES NOT SHOW LOCATIONS OF HVAC SMOKE | | DETECTORS; HOWEVER, INSTALLATION IS REFERENCED | | ELSEWHERE ON SEPARATE SHEETS. HVAC SD'S SHALL BE | | INSTALLED PER NFPA 90A AND SHALL BE INSPECTED AND | | TESTED BY A FIRE INSPECTOR. | | | | SHEET SP, THE SHADED OCCUPANY IS INDICATED AS E-2, EACH | | PLAN SHEET IS INDICATED AS "STE # 03", CLARIFICATION | | MAY BE NECESSARY. |
|