Plan Review Notes For Permit 14051109 |
Permit Number |
14051109 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-06-04 16:31:27 | PROJECT: 3010 N. FLAGLER DR. | | | | 2ST REVIEW ELECTRICAL. | | ACTION: PROVISO ATTACHED WITH COMMENTS FROM CONTRACTOR. | | | | CODE REFERENCED: 2008 EDITION OF THE NEC AND THE 2010 | | EDITION OF THE FLORIDA BUILDING CODE. | | | | 1) INDICATE CIRCUITRY ON FLOOR PLAN. FBC 107.2.1 | | ACCORDING TO THE MECHANICAL PLANS THE AHU IS BEING | | RELOCATED TO THE ATTIC. PLEASE INDICATE THE ELECTRICAL | | CIRCUITRY THAT WILL FEED THE AHU IN IT'S NEW LOCATION. | | | | 2) INDICATE DISCONNECTS WHERE REQUIRED AT A/C EQUIPMENT | | ETC.. NEC 440.14 | | | | 3) GFCI OUTLET REQUIRED AT A/C EQUIPMENT. NEC 210.63 | | | | 4) INDICATE REQUIRED BATHROOM OUTLET PER NEC 210.52(D), | | 210.8 | | | | 5) INDICATE A SMOKE DETECTION SYSTEM AS REQUIRED PER | | FBC-R 314, 315 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR AT [email protected] |
|