2014-06-04 16:31:27PROJECT: 3010 N. FLAGLER DR.
  
 2ST REVIEW ELECTRICAL.
 ACTION: PROVISO ATTACHED WITH COMMENTS FROM CONTRACTOR.
  
 CODE REFERENCED: 2008 EDITION OF THE NEC AND THE 2010
 EDITION OF THE FLORIDA BUILDING CODE.
  
 1) INDICATE CIRCUITRY ON FLOOR PLAN. FBC 107.2.1
 ACCORDING TO THE MECHANICAL PLANS THE AHU IS BEING
 RELOCATED TO THE ATTIC. PLEASE INDICATE THE ELECTRICAL
 CIRCUITRY THAT WILL FEED THE AHU IN IT'S NEW LOCATION.
  
 2) INDICATE DISCONNECTS WHERE REQUIRED AT A/C EQUIPMENT
 ETC.. NEC 440.14
  
 3) GFCI OUTLET REQUIRED AT A/C EQUIPMENT. NEC 210.63
  
 4) INDICATE REQUIRED BATHROOM OUTLET PER NEC 210.52(D),
 210.8
  
 5) INDICATE A SMOKE DETECTION SYSTEM AS REQUIRED PER
 FBC-R 314, 315
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]