Plan Review Notes
Plan Review Notes For Permit 14051075
Permit Number 14051075
Review Stop E
Sequence Number 1
Notes
Date Text
2014-05-30 12:07:53ELECTRICAL. 1ST REVIEW DENIED. BASED ON THE 2008
 EDITION OF THE NEC AND THE 2010 FBC. SEE COMMENTS
 BELOW:
  
 1) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. FBC R314, 315
  
 2) THE SERVICE DISCONNECTING MEANS SHALL BE INSTALLED
 AT A READILY ACCESSIBLE LOCATION INSIDE OR OUTSIDE THE
 BUILDING NEAREST THE POINT OF SERVICE ENTRANCE. NEC
 230.70
  
 3) AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND. NEC 250.94
  
 4) BATHROOM BRANCH CIRCUITS IN ADDITION TO THE NUMBER
 OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS OF THIS
 SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS. NEC 210.11 (C)(3)
  
 5) NOTE ON THE PLAN THE REQUIREMENT FOR TAMPER
 RESISTANT RECEPTACLES. NEC 406.11
  
 6) AT LEAST ONE SWITCH CONTROLLED LIGHTING OUTLET SHALL
 BE PROVIDED ON THE EXTERIOR SIDE OF THE SIDE ENTRANCE.
 NEC 210.70 (A) (2) (B).
  
 7) AT LEAST ONE LIGHTING OUTLET SHALL BE PROVIDED IN
 UTILITY ROOMS AND BASEMENTS WHERE SUCH SPACES ARE USED
 FOR STORAGE OR CONTAIN EQUIPMENT REQUIRING SERVICE.
 FBC-EXISTING 708.3.6, NEC 210.70
  
 8) PROVIDE A RECEPTACLE OUTLET IN THE HALLWAY. NEC
 210.52(H)
  
 9) INDICATE ALL CIRCUITRY ON FLOOR PLAN AND COMPLETE
 PANEL SCHEDULE INCLUDING ALL CIRCUITRY INDICATED ON
 FLOOOR PLAN. FBC 107.3.5.3 (WPB)
  
 10) ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC
 406.11 THOSE OUTLETS IN WET LOCATIONS SHALL BE WEATHER
 RESISTANT NEC 406.8(B)(1)
  
 11) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. NEC 210.8
  
 12) GFCI PROTECTED OUTLETS ARE REQUIRED FRONT AND BACK
 AT EACH RESIDENTIAL BUILDING AND AT THE LOCATION OF THE
 MECHANICAL EQUIPMENT. NEC 210-52 (E) (1), 210-63
  
  