Plan Review Notes
Plan Review Notes For Permit 14051075
Permit Number 14051075
Review Stop B
Sequence Number 1
Notes
Date Text
2014-05-31 13:25:441ST REVIEW:
  
 THE PERMIT AND PLAN SHOULD CONTAIN PER FBC
 107.3.5.3.1(5) - WIND DESIGN LOADS/DESIGN PRESSURES
 PURSUANT TO FBCR, CHAPTER 3. THIS IS APPLICABLE TO
 WINDOW REPALCEMENT, THE WINDOW TO BE REMOVED AND THE
 WALL TO BE FILLED IN AT THAT LOCATION. RESULTING DESIGN
 PRESSURE ARE APPLICABLE TO THE REPLACEMENT OF THE
 SIDING. THE PRODUCT APPROVAL FOR THE REPALCEMENT SIDING
 INDICATES IT IS TO BE PLACED OVER 5/8" 5PLY APA RATED
 PLYWOOD SHEATHING. THE PLAN PROVIDED FOR THE EXISTING
 CONDITION SHOWS 1/2" 3 PLY SHEATHING. THIS SHOULD BE
 EVALUATED AND PERHAPS ENGINEERED TO INDICATE COMPLIANCE
 WITH THE EXISTING BUILDING CODE FOR AN ALTERATION LEVEL
 ONE OR PERSCRIPTIVE PER FBCEB 301.2.2 NEW AND
 REPLACEMENT MATERIALS. PROVIDE IMPACT PROTECTION FOR
 FOR GLAZING.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710