2014-05-31 13:25:44 | 1ST REVIEW: | | | | THE PERMIT AND PLAN SHOULD CONTAIN PER FBC | | 107.3.5.3.1(5) - WIND DESIGN LOADS/DESIGN PRESSURES | | PURSUANT TO FBCR, CHAPTER 3. THIS IS APPLICABLE TO | | WINDOW REPALCEMENT, THE WINDOW TO BE REMOVED AND THE | | WALL TO BE FILLED IN AT THAT LOCATION. RESULTING DESIGN | | PRESSURE ARE APPLICABLE TO THE REPLACEMENT OF THE | | SIDING. THE PRODUCT APPROVAL FOR THE REPALCEMENT SIDING | | INDICATES IT IS TO BE PLACED OVER 5/8" 5PLY APA RATED | | PLYWOOD SHEATHING. THE PLAN PROVIDED FOR THE EXISTING | | CONDITION SHOWS 1/2" 3 PLY SHEATHING. THIS SHOULD BE | | EVALUATED AND PERHAPS ENGINEERED TO INDICATE COMPLIANCE | | WITH THE EXISTING BUILDING CODE FOR AN ALTERATION LEVEL | | ONE OR PERSCRIPTIVE PER FBCEB 301.2.2 NEW AND | | REPLACEMENT MATERIALS. PROVIDE IMPACT PROTECTION FOR | | FOR GLAZING. | | | | STEVEN KENNEDY, CBO | | CHIEF PLANS EXAMINER | | (561) 805-6710 | | [email protected] | | |
|