2014-06-05 11:42:17PLUMBING PLAN REVIEW
 PERMIT: 14060141
 ADD: 1106 FLORIDA AVE.
 CONT: GANNAWAY INC
 TEL: (561)557-3596
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JUNE 05/2014
 ACTION: DENIED
  
 1) THE SUBMITTED PLAN DOES NOT SHOW ENOUGH DETAIL TO
 DETERMINE CODE COMPLIANCE. THE REVISION FORM INDICATES
 THE RENOVATION OF A BATHROOM WITH THE RELOCATION OF THE
 WATER CLOSET AND SHOWER. NO FLOOR PLAN WAS SUBMITTED
 WITH THIS REVISION. 2010 WEST PALM BEACH AMENDMENTS TO
 THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 PLEASE PROVIDE DOMENSIONS OF THE ROOM AS WELL AS FROM
 THE WALL TO THE CENTER OF FIXTURES. 2010 FBC-R 307.1
 AND FIGURE R307.1 MINIMUM FIXTURE CLEARANCES CAN NOT BE
 DETERMINED.
  
 2) COMPLIANCE WITH MINIMUM SHOWER COMPARTMENT SIZES CAN
 NOT BE DETERMINED 2010 FBC-P2708.1
  
 3) COMPLIANCE WITH 2010 FBC-P2709.2 LINING REQUIRED,
 PLEASE PROVIDE SHOWER PAN LINING MATERIALS.
  
 4) PROVIDE COMPLIANCE WITH 2010 FBC-P BATHTUB AND
 SHOWER SPACES. SHOWER WALLS SHALL BE FINISHED IN
 ACCORDANCE WITH SECTION R307.2. R307.2 BATHTUB AND
 SHOWER SPACES. BATHTUB AND SHOWER FLOORS AND WALLS
 ABOVE BATHTUBS WITH INSTALLED SHOWER HEADS AND IN
 SHOWER COMPARTMENTS SHALL BE FINISHED WITH A
 NONABSORBENT SURFACE. SUCH WALL SURFACES SHALL EXTEND
 TO A HEIGHT OF NOT LESS THAN 6 FEET (1829 MM) ABOVE THE
 FLOOR.
  
 5) THE REVISION SUBMITTED WITH A PLUMBING SANITARY
 ISOMETRIC SHOWS A DRY VENT WITH THE WASTE DEAD ENDING
 INTO THE STUDOR VENT. P3108.2 DRY VENT CONNECTION.
 THE REQUIRED DRY-VENT CONNECTION FOR WET-VENTED SYSTEMS
 SHALL COMPLY WITH SECTIONS P3108.2.1 AND P3108.2.2.
  
 P3108.2.1 HORIZONTAL WET VENT.
 THE DRY-VENT CONNECTION FOR A HORIZONTAL WET-VENT
 SYSTEM SHALL BE AN INDIVIDUAL VENT OR A COMMON VENT FOR
 ANY BATHROOM GROUP FIXTURE, EXCEPT AN EMERGENCY FLOOR
 DRAIN. WHERE THE DRY VENT CONNECTS TO A WATER CLOSET
 FIXTURE DRAIN, THE DRAIN SHALL CONNECT HORIZONTALLY TO
 THE HORIZONTAL WET VENT SYSTEM. NOT MORE THAN ONE
 WET-VENTED FIXTURE DRAIN SHALL DISCHARGE UPSTREAM OF
 THE DRY-VENTED FIXTURE DRAIN CONNECTION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  