Plan Review Notes For Permit 14051048 |
Permit Number |
14051048 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-06-02 17:09:16 | NOT ENOUGH DETAIL ON THE SUBMITTED DRAWING TO | | ACCURATELY DETERMINE THE WORK BEING DONE. | | | | I WILL NEED THE FOLLOWING ADDED TO THE DRAWINGS FOR A | | SUCCESSFUL ELECTRICAL REVIEW: | | | | 1. IDENTIFY WHICH IS BLDG. FORTON AND BLDG.SANDER | | 2. PROVIDE A DETAIL DESCRIPTION OF THE PROPOSED FEEDER. | | 3. SUBMIT A LOAD CALC TO DETERMINE THAT PROPER SIZE OF | | THE FEEDER. | | 4. INCLUDE ON THE DRAWING CONDUCTOR SIZING AND | | INSULATION. | | | | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL | | PLANS EXAMINER | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | FOLLOWING LINK: | | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | US.ASPX | | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | ABOVE THE SECOND PERMIT INFORMATION). | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR | | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER | | PERMIT CONDITIONS. | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | I CAN BE REACHED AT 561-805-6718 OR | | [email protected] | | |
|