Plan Review Notes
Plan Review Notes For Permit 14051048
Permit Number 14051048
Review Stop E
Sequence Number 1
Notes
Date Text
2014-06-02 17:09:16NOT ENOUGH DETAIL ON THE SUBMITTED DRAWING TO
 ACCURATELY DETERMINE THE WORK BEING DONE.
  
 I WILL NEED THE FOLLOWING ADDED TO THE DRAWINGS FOR A
 SUCCESSFUL ELECTRICAL REVIEW:
  
 1. IDENTIFY WHICH IS BLDG. FORTON AND BLDG.SANDER
 2. PROVIDE A DETAIL DESCRIPTION OF THE PROPOSED FEEDER.
 3. SUBMIT A LOAD CALC TO DETERMINE THAT PROPER SIZE OF
 THE FEEDER.
 4. INCLUDE ON THE DRAWING CONDUCTOR SIZING AND
 INSULATION.
  
 THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL
 PLANS EXAMINER
 YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE
 FOLLOWING LINK:
  
 HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT
 US.ASPX
  
 ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS
 EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER,
 AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB
 ABOVE THE SECOND PERMIT INFORMATION).
 AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR
 COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER
 PERMIT CONDITIONS.
 FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME.
 I CAN BE REACHED AT 561-805-6718 OR
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved