2014-07-16 15:02:25 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. CALCULATIONS PREPARED BY JUSTIN PLAISTED. AN |
| ENGINEERING LICENSE IS REQUIRED TO PRACTICE ENGINEERING |
| IN FLORIDA, FS471. |
| |
| 2. DESIGNER RESPONSIBILITY NOT CLEAR. JUSTIN PLAISTED |
| PREPARED THE CALCS, BUT THEY ARE SIGNED AND SEALED BY |
| JOHN HOLT, PE. PLEASE CLARIFY. |
| |
| 3. DESIGN CRITERIA NOT CLEAR, FBC 1609. JUSTIN PLAISTED |
| HAS PERFORMED CALCULATIONS PER NAAMM FP 1001-07, 100 |
| MPH. PLEASE REFER MR. PLAISTED TO THE MAP IN NAAMM FP |
| 1001-07, WHICH INCLUDES THE WIND SPEED MAP FROM |
| ASCE7-05. THE CITY OF WEST PALM BEACH LIES ENTIRELY IN |
| THE 140MPH ZONE IN THIS MAP. |
| |
| JOHN HOLT, UNDER HIS SEAL, DECLARES THE DESIGN CRITERIA |
| AS 180MPH EXPOSURE C. AS THE COMBINED STRESS RATION IS |
| .96, THERE APPEARS TO BE A DISCREPANCY IN THE DESIGN |
| CRITERA ATTESTED TO BY THE ENGINEER. |
| |
| NEW COMMENT: |
| |
| 4. THIS PARCEL IS LOCATED IN A SPECIAL HAZARD FLOOD |
| ZONE A8 (15' BFE). THIS PROPOSED IMPROVEMENT IS TO |
| RESIST FLOOD LOADS AND FLOOD DESIGN DATA TO BE INCLUDED |
| ON THE PLAN, FBC 1603.1.7. |
| |
| IF AVAILABLE, PLEASE PROVIDE THE ELEVATION CERTIFICATE |
| FOR THIS PROPERTY. IF PROPOSED IMPROVEMENT IS HIGHER |
| THAN DESIGN FLOOD ELEVATION, FLOOD DESIGN LOAD DATA IS |
| NOT REQUIRED. AN ELEVATION CERTIFICATE HAS ALREADY BEEN |
| REQUESTED RELATED TO ANOTHER PERMIT. |
| |
| A SET HAS BEEN RETAINED. |
| |