2014-06-13 15:15:41 | PLUMBING PLAN REVIEW |
| PERMIT: 14050989 |
| ADD: 207 6TH ST |
| CONT: FINE LINE CONSTRUCTION |
| TEL: (561)582-7880 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. JUNE 13/2014 |
| ACTION: DENIED |
| |
| 1) THE SANITARY ISOMETRIC IS DRAWN WITH THE RESTROOMS |
| USING HORIZONTAL WET VENTS. PLEASE SEE THE CODE SECTION |
| INDICATES WET VENTS ARE TO BE INSTALLED IN BATHROOMS (1 |
| & 2 FAMILY) ALSO SEE BOAF INFORMAL INTERPRETATION. |
| |
| DATE: MON APR 13 2009 |
| REPORT: 6090 |
| CODE: PLUMBING CODE YEAR: 2007 |
| SECTION: 909 |
| QUESTION: |
| IS IT THE INTENT OF THE FLORIDA BUILDING CODE - |
| PLUMBING SECTION 909 TO ALLOW A URINAL TO WET VENT A |
| SINGLE COMMERCIAL |
| WATER CLOSET OR TO DRAIN INTO THAT WATER CLOSET?S |
| INDIVIDUAL VENT? |
| COMMENT: |
| ANSWER: |
| NO. ONLY FIXTURES IN BATHROOM GROUPS AS DEFINED IN |
| FLORIDA BUILDING CODE - PLUMBING CHAPTER 2 ARE |
| PERMITTED TO |
| CONNECT TO THE WET VENT. ANY ADDITIONAL FIXTURES MUST |
| DISCHARGE DOWNSTREAM OF THE WET VENT. |
| COMMENTARY: |
| A URINAL IS NOT INCLUDED IN THE DEFINITION OF A |
| BATHROOM GROUP. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |