Plan Review Notes
Plan Review Notes For Permit 14050989
Permit Number 14050989
Review Stop E
Sequence Number 1
Notes
Date Text
2014-06-09 16:24:566/9/14.
 PROJECT: HOPKINS MARINE.
 PERMIT#: 14050989
 CODE: 2008 EDITION OF THE NEC AND THE 2010 EDITION OF
 THE FBC
 ACTION: APPROVED WITH PROVISO:
  
 1) PARTITIONS OF THE FREESTANDING TYPE (NOT FIXED)
 SHALL BE PERMITTED TO BE CONNECTED TO THE BUILDING
 ELECTRICAL SYSTEM BY ONE OF THE WIRING METHODS OF
 CHAPTER 3. MULTIWIRE BRANCH CIRCUITS SUPPLYING POWER TO
 PERMANENTLY CONNECTED FREESTANDING PARTITIONS SHALL BE
 PROVIDED WITH A MEANS TO DISCONNECT SIMULTANEOUSLY ALL
 UNGROUNDED CONDUCTORS AT THE PANELBOARD WHERE THE
 BRANCH CIRCUIT ORIGINATES. NEC 605.7
  
 2) EACH MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH
 A MEANS THAT WILL SIMULTANEOUSLY DISCONNECT ALL
 UNGROUNDED CONDUCTORS AT THE POINT WHERE THE BRANCH
 CIRCUIT ORIGINATES. 210.4(B)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]