2014-06-13 15:00:43 | BUILDING PLAN REVIEW |
| PERMIT: 14050989 |
| ADD: 207 6TH ST |
| CONT: FINE LINE CONSTRUCTION |
| TEL: (561)582-7880 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRI. JUNE 13/2014 |
| ACTION: DENIED |
| |
| 1) PLEASE PROVIDE A SURVEY OF THE PROPERTY, THE SITE |
| PLAN DOES NOT MATCH TTHE LOT CONFIGURATION FOUND WITH |
| THE PROPERTY APPRAISERS WEB SITE. |
| THE SECOND ISSUE IS TO DETERMINE IF THIS BUILDING IS IN |
| A A5 FLOOD ZONE. 107.2.1.3 ADDITIONAL INFORMATION IS |
| REQUIRED. IF FLOOD ZONE THEN FLOOD ZONE CERTIFICATES |
| WILL BE REQUIRED AND THE FLOOR ELEVATION OF THE 1ST |
| FLOOR. |
| |
| 2) SHEET A-1.0: |
| 2A) BOTH THE MENS(125) & WOMENS (126) RESTROOMS HAVE |
| WITHIN THEM ACCESSIBLE TOLIET COMPARTMENTS (STALLS) |
| PLEASE SEE 2010 FBC-ACCESSIBLITY CODE SECTION 604.8.1.2 |
| FOR DOOR SWING. TOILET COMPARTMENT DOORS SHALL NOT |
| SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA. THE |
| DOORS SWING IN OVER THE REQUIED CLEAR AREA FOR THE LAV. |
| |
| 2B) NO ACTION TO BE TAKEN. THE PLANS DO NOT PROVIDE |
| VERTICAL ACCESSIBILITY TO THE MEZZANINE AREA. 201.1.1, |
| IT APPEARS THE EXCEPTIONS , EXCEPTION # 2 FOR STORAGE |
| AND EXCEPTION # 3 FOR OCCUPIABLE SPACES AND PRIVATE |
| OFFICE. |
| |
| 3) SHEET S-4.1 SHOWS THE DESIGN LOADS BUT THERE ARE NO |
| DESIGN LOADS FOR THE STAIRS OR MEZZANINE FOR THE OFFICE |
| OR THE STORAGE PORTION OF THE MEZZANINE, WILL THE |
| MEZZANINE BEDESIGNED FOR LIGHT OR HEAVY? FBC-B TABLE |
| 1607.1. |
| |
| 4) PLANS DO NOT SHOW CODE COMPLIANCE WITH 2010 FL |
| ACCESSIBILTY 211.2 MINIMUM NUMBER. |
| NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| 602.7. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| NOTE NO ROOFING PRODUCT APPROVALS WERE SUBMITTED. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |