Plan Review Notes
Plan Review Notes For Permit 14050989
Permit Number 14050989
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-13 15:00:43BUILDING PLAN REVIEW
 PERMIT: 14050989
 ADD: 207 6TH ST
 CONT: FINE LINE CONSTRUCTION
 TEL: (561)582-7880
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JUNE 13/2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE A SURVEY OF THE PROPERTY, THE SITE
 PLAN DOES NOT MATCH TTHE LOT CONFIGURATION FOUND WITH
 THE PROPERTY APPRAISERS WEB SITE.
 THE SECOND ISSUE IS TO DETERMINE IF THIS BUILDING IS IN
 A A5 FLOOD ZONE. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. IF FLOOD ZONE THEN FLOOD ZONE CERTIFICATES
 WILL BE REQUIRED AND THE FLOOR ELEVATION OF THE 1ST
 FLOOR.
  
 2) SHEET A-1.0:
 2A) BOTH THE MENS(125) & WOMENS (126) RESTROOMS HAVE
 WITHIN THEM ACCESSIBLE TOLIET COMPARTMENTS (STALLS)
 PLEASE SEE 2010 FBC-ACCESSIBLITY CODE SECTION 604.8.1.2
 FOR DOOR SWING. TOILET COMPARTMENT DOORS SHALL NOT
 SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA. THE
 DOORS SWING IN OVER THE REQUIED CLEAR AREA FOR THE LAV.
  
 2B) NO ACTION TO BE TAKEN. THE PLANS DO NOT PROVIDE
 VERTICAL ACCESSIBILITY TO THE MEZZANINE AREA. 201.1.1,
 IT APPEARS THE EXCEPTIONS , EXCEPTION # 2 FOR STORAGE
 AND EXCEPTION # 3 FOR OCCUPIABLE SPACES AND PRIVATE
 OFFICE.
  
 3) SHEET S-4.1 SHOWS THE DESIGN LOADS BUT THERE ARE NO
 DESIGN LOADS FOR THE STAIRS OR MEZZANINE FOR THE OFFICE
 OR THE STORAGE PORTION OF THE MEZZANINE, WILL THE
 MEZZANINE BEDESIGNED FOR LIGHT OR HEAVY? FBC-B TABLE
 1607.1.
  
 4) PLANS DO NOT SHOW CODE COMPLIANCE WITH 2010 FL
 ACCESSIBILTY 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 NOTE NO ROOFING PRODUCT APPROVALS WERE SUBMITTED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  