2014-07-08 10:19:19PLUMBING PLAN REVIEW
 PERMIT: 14050974
 ADD: 525 S FLAGLER DR # GPH3
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561)284-3722
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JULY 08/2014
 ACTION: DENIED
  
 1)) SHEETS D-100 & A-100 SHOW THE REMOVAL OF A TUB AND
 NEW LOCATION FOR THE WATER CLOSET & BIDET. THERE IS NO
 FLAT SANITARY NOR SANITARY ISOMETRIC DIAGRAM SHOWING
 THE NEW SANITARY PIPING AND VENTING OF THESE FIXTURES.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.3 PLUMBING
 1. MINIMUM PLUMBING FIXTURE CLEARANCES BIDET TO WATER
 CLOSET FBC-P FIGURE 405.3.1.
 2. FIXTURE REQUIREMENTS
 3. SANITARY DRAINAGE & VENTS
  
 3) A LETTER FROM THE CONDOMINIUM BOARD OR OWNER OF UNIT
 BELOW GIVING APPROVAL FORACCESS TO WORK IN THEIRE UNIT.
 HOW WILL THE FLOOR FIRE RATING BE MAINTAINED.
 2010 FBC-P 307.3 PENETRATIONS OF FLOOR/CEILING
 ASSEMBLIES AND FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS OF FLOOR/CEILING ASSEMBLIES AND ASSEMBLIES
 REQUIRED TO HAVE A FIRE-RESISTANCE RATING SHALL BE
 PROTECTED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 BUILDING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  