2014-07-08 10:19:19 | PLUMBING PLAN REVIEW |
| PERMIT: 14050974 |
| ADD: 525 S FLAGLER DR # GPH3 |
| CONT: CAMBRIDGE CONSTRUCTION |
| TEL: (561)284-3722 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: TUES. JULY 08/2014 |
| ACTION: DENIED |
| |
| 1)) SHEETS D-100 & A-100 SHOW THE REMOVAL OF A TUB AND |
| NEW LOCATION FOR THE WATER CLOSET & BIDET. THERE IS NO |
| FLAT SANITARY NOR SANITARY ISOMETRIC DIAGRAM SHOWING |
| THE NEW SANITARY PIPING AND VENTING OF THESE FIXTURES. |
| 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION107.3.5 MINIMUM PLAN |
| REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.3 PLUMBING |
| 1. MINIMUM PLUMBING FIXTURE CLEARANCES BIDET TO WATER |
| CLOSET FBC-P FIGURE 405.3.1. |
| 2. FIXTURE REQUIREMENTS |
| 3. SANITARY DRAINAGE & VENTS |
| |
| 3) A LETTER FROM THE CONDOMINIUM BOARD OR OWNER OF UNIT |
| BELOW GIVING APPROVAL FORACCESS TO WORK IN THEIRE UNIT. |
| HOW WILL THE FLOOR FIRE RATING BE MAINTAINED. |
| 2010 FBC-P 307.3 PENETRATIONS OF FLOOR/CEILING |
| ASSEMBLIES AND FIRE-RESISTANCE-RATED ASSEMBLIES. |
| PENETRATIONS OF FLOOR/CEILING ASSEMBLIES AND ASSEMBLIES |
| REQUIRED TO HAVE A FIRE-RESISTANCE RATING SHALL BE |
| PROTECTED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| BUILDING. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |