Plan Review Notes
Plan Review Notes For Permit 14050974
Permit Number 14050974
Review Stop E
Sequence Number 2
Notes
Date Text
2014-07-10 16:57:03DATE: 7/9/2014
 PROJECT: DREYFOSS RESIDENCE
 PERMIT#: 14050974
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) AN ELECTRICAL PERMIT IS REQUIRED. THE WRITTEN SCOPE
 OF WORK DOES NOT CALL OUT SPECIFIC ELECTRICAL WORK
 HOWEVER THE CODE REQUIRES ELECTRICAL WORK. SEE BELOW:
  
 2) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314.3.1
  
 3) AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE
 PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH
 CIRCUITS SHALL HAVE NO OTHER OUTLETS.PROVIDE A 20
 AMPERE BRANCH CIRCUIT FOR THE BATHROOM. NEC 210.11
 (C)(3)
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]