2014-06-05 19:18:16 | PLUMBING PLAN REVIEW |
| PERMIT: 14050974 |
| ADD: 525 S FLAGLER DR # GPH3 |
| CONT: CAMBRIDGE CONSTRUCTION |
| TEL: (561)284-3722 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURSDAY JUNE 05/2014 |
| ACTION: DENIED |
| |
| 1) PLANS SEALED BY OUT OF STATE ARCHITECT. FLORIDA |
| ADMINISTRATIVE RULE 61G1-16.002 DESCRIPTION OF SEAL. |
| (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE |
| ARCHITECT OR INTERIOR DESIGNER AND THE REGISTRATION |
| NUMBER; THE SEAL OF THE ARCHITECT SHALL BE CIRCULAR, |
| AND THE SEAL OF THE INTERIOR DESIGNER SHALL BE |
| HEXAGONAL. BOTH SEALS SHALL BE APPROXIMATELY 2" IN |
| DIAMETER WITH TWO CIRCULAR LINES BETWEEN WHICH LINES |
| SHALL APPEAR, AT THE TOP, THE WORDS ?STATE OF FLORIDA? |
| AND AT THE BOTTOM THE WORDS ?REGISTERED ARCHITECT? OR |
| ?LICENSED INTERIOR DESIGNER,? WHICHEVER IS APPLICABLE. |
| |
| 2) SHEETS D-100 & A-100 SHOW THE REMOVAL OF A TUB AND |
| NEW LOCATION FOR THE WATER CLOSET & BIDET. THERE IS NO |
| FLAT SANITARY NOR SANITARY RISER DIAGRAM SHOWING THE |
| NEW SANITARY PIPING AND VENTING OF THESE FIXTURES. 2010 |
| WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| CODE, CHAPTER 1, ADMINISTRATION107.3.5 MINIMUM PLAN |
| REVIEW CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.3 PLUMBING |
| 1. MINIMUM PLUMBING FIXTURE CLEARANCES BIDET TO WATER |
| CLOSET FBC-P FIGURE 405.3.1. |
| 2. FIXTURE REQUIREMENTS |
| 3. WATER SUPPLY PIPING |
| 4. SANITARY DRAINAGE |
| 5. VENTS |
| 6.PLUMBING RISE |
| |
| 3) THE SANITARY WASTE WILL BE ROUTED THROUGH THE FLOOR |
| BELOW HOW WILL THE CONTRACTOR GAIN ENTRY. HOW WILL THE |
| FLOOR FIRE RATING BE MAINTAINED. |
| 2010 FBC-P 307.3 PENETRATIONS OF FLOOR/CEILING |
| ASSEMBLIES AND FIRE-RESISTANCE-RATED ASSEMBLIES. |
| PENETRATIONS OF FLOOR/CEILING ASSEMBLIES AND ASSEMBLIES |
| REQUIRED TO HAVE A FIRE-RESISTANCE RATING SHALL BE |
| PROTECTED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| BUILDING. |
| |