Plan Review Notes For Permit 14050974 |
Permit Number |
14050974 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-07-10 16:57:42 | DATE: 7/9/2014 | | PROJECT: DREYFOSS RESIDENCE | | PERMIT#: 14050974 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | 1) AN ELECTRICAL PERMIT IS REQUIRED. THE WRITTEN SCOPE | | OF WORK DOES NOT CALL OUT SPECIFIC ELECTRICAL WORK | | HOWEVER THE CODE REQUIRES ELECTRICAL WORK. SEE BELOW: | | | | 2) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL | | 314.3.1 | | | | 3) AT LEAST ONE 20-AMPERE BRANCH CIRCUIT SHALL BE | | PROVIDED TO SUPPLY BATHROOM RECEPTACLE OUTLET(S). SUCH | | CIRCUITS SHALL HAVE NO OTHER OUTLETS.PROVIDE A 20 | | AMPERE BRANCH CIRCUIT FOR THE BATHROOM. NEC 210.11 | | (C)(3) | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|