2014-07-17 12:02:22 | DATE: 7/14/2014 |
| PROJECT: MALVERNE RESIDENCE |
| PERMIT#: 14050937 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 3RD ELECTRICAL PLAN REVIEW |
| ACTION: PROVISO |
| |
| 1) AN INTER SYSTEM BOND IS REQUIRED AT THE SERVICE. NEC |
| 250.94. |
| |
| 2) A SWITCH CONTROLLED LIGHT IS REQUIRED AT THE ATTIC |
| ACCESS. FOR ATTICS, UNDERFLOOR SPACES, UTILITY ROOMS, |
| AND BASEMENTS, AT LEAST ONE LIGHTING OUTLET CONTAINING |
| A SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE |
| INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR |
| CONTAIN EQUIPMENT REQUIRING SERVICING. AT LEAST ONE |
| POINT OF CONTROL SHALL BE AT THE USUAL POINT OF ENTRY |
| TO THESE SPACES. THE LIGHTING OUTLET SHALL BE PROVIDED |
| AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. NEC |
| 210.70(3) |
| |
| 3) INDICATE A SMOKE AND C/O DETECTION SYSTEM AS |
| REQUIRED PER FBC-R 314, 315 |
| "EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| ROOM USED FOR SLEEPING PURPOSES". FBC-R 315.1 |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |