2014-06-12 15:36:50 | PROJECT: 210 MALVERNE RD. |
| |
| 2ND ELECTRICAL.REVIEW |
| |
| ACTION: FAILED |
| |
| CODE REFERENCED: 2008 EDITION OF THE NEC AND THE 2010 |
| EDITION OF THE FLORIDA BUILDING CODE. |
| |
| 1) A GROUNDING ELECTRODE SYSTEM IS REQUIRED AT THE |
| SERVICE. NEC 250.50. |
| |
| 2) AN INTER SYSTEM BOND IS REQUIRED AT THE SERVICE. NEC |
| 250.94. |
| |
| 3) INDICATE ALL REQUIRED OUTLETS PER NEC 210.52. |
| |
| 4) INDICATE A SMOKE DETECTION SYSTEM AS REQUIRED PER |
| FBC-R 314, 315 |
| |
| 5) INDICATE CIRCUITRY ON FLOOR PLAN. FBC 107.2.1 |
| |
| 6) INDICATE DISCONNECTS WHERE REQUIRED AT A/C EQUIPMENT |
| ETC.. NEC 440.14 |
| |
| 7) GFCI OUTLET REQUIRED AT A/C EQUIPMENT. NEC 210.63 |
| |
| NOTE: FBC 107.2.1 STATES IN PART: |
| "CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN" |
| |
| THEREFORE. PER THE FBC 107.2.1 AS STATED ABOVE, |
| ADDITIONAL CLARIFICATION IS REQUIRED TO CLARIFY THE |
| SCOPE OF WORK: |
| |
| 8) THE PERSON RESPONSIBLE FOR THE DESIGN IS REQUIRED TO |
| PUT THEIR NAME AND SIGNATURE ON THE PLAN. |
| |
| 9) INDICATE SPECIFICALLY WHAT IS EXISTING TO REMAIN AND |
| WHAT IS PROPOSED TO BE NEW. |
| |
| 10) INDICATE THE LOCATION OF THE SERVICE AND THE |
| ELECTRICAL PANELS. |
| |
| 11) INDICATE THE NAMES AND LOCATIONS OF ROOMS. EG. |
| "BEDROOM, KITCHEN LIVINGROOM" AND SEPARATION OF |
| APARTMENTS OR EFFICIENCIES. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR AT [email protected] |