Plan Review Notes
Plan Review Notes For Permit 14050931
Permit Number 14050931
Review Stop E
Sequence Number 1
Notes
Date Text
2014-06-02 07:42:35PROJECT: 210 MALVERNE RD.
  
 1ST REVIEW ELECTRICAL.
  
 ACTION: FAILED
  
 CODE REFERENCED: 2008 EDITION OF THE NEC AND THE 2010
 EDITION OF THE FLORIDA BUILDING CODE.
  
 COMMENTS:
  
 1) A GROUNDING ELECTRODE SYSTEM IS REQUIRED AT THE
 SERVICE. NEC 250.50.
  
 2) AN INTER SYSTEM BOND IS REQUIRED AT THE SERVICE. NEC
 250.94.
  
 3) INDICATE ALL REQUIRED OUTLETS PER NEC 210.52.
  
 4) INDICATE A SMOKE DETECTION SYSTEM AS REQUIRED PER
 FBC-R 314, 315
  
 5) INDICATE CIRCUITRY ON FLOOR PLAN. FBC 107.2.1
  
 6) INDICATE DISCONNECTS WHERE REQUIRED AT A/C EQUIPMENT
 ETC.. NEC 440.14
  
 7) GFCI OUTLET REQUIRED AT A/C EQUIPMENT. NEC 210.63
  
 NOTE: FBC 107.2.1 STATES IN PART:
 "CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN"
  
 THEREFORE. PER THE FBC 107.2.1 AS STATED ABOVE,
 ADDITIONAL CLARIFICATION IS REQUIRED TO CLARIFY THE
 SCOPE OF WORK:
  
 8) THE PERSON RESPONSIBLE FOR THE DESIGN IS REQUIRED TO
 PUT THEIR NAME AND SIGNATURE ON THE PLAN.
  
 9) INDICATE SPECIFICALLY WHAT IS EXISTING TO REMAIN AND
 WHAT IS PROPOSED TO BE NEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]