2014-05-28 09:32:13 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) PROVIDE 2 SETS OF A FLOOR/CEILING PLAN THAT SHOWS | | THE DIMENSIONS AND LOCATION OF THE NEW KITCHEN SOFFIT. | | SHOW LOCATIONS OF THE FIRE SPRINKLER HEADS AND SHOW | | THAT THEY WILL NOT BE AFFECTED BY THE NEW SOFFIT. CITY | | AMENDMENTS 107.2.1 | | | | 2) PROVIDE 2 SETS OF A FRAMING DETAIL INDICATING HOW | | THE SOFFIT WILL BE CONSTRUCTED AND THE MATERIALS THAT | | WILL BE USED. CITY AMENDMENTS 107.2.1 AND FBC 805.1 | | | | 3) CLARIFY THAT THE KITCHEN CABINETS ARE BEING REPLACED | | IN THE EXISTING CONFIGURATION. IF THE CABINET LAYOUT IS | | BEING ALTERED SUBMIT TWO SETS OF PLANS SHOWING THE | | ALTERATIONS. CITY AMENDMENTS 107.2.1 | | | | 4) THE ADDRESS OF THE JOB AND THE PRINTED NAME, | | SIGNATURE AND LICENSE NUMBER OF THE PERSON RESPONSIBLE | | FOR THE DESIGN IS REQUIRED ON THE PLANS. CITY | | AMENDMENTS 107.2.1, FS 471 AND FS 481 | | | | 5) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS AND TESTING INFORMATION FOR THE SOUND | | INSULATING UNDERLAYMENT THAT IS REQUIRED UNDER THE TILE | | FLOORING. SHOW THAT IT COMPLIES WITH FBC 1207.2 | | AIR-BORNE AND FBC 1207.3 STRUCTURE-BORNE SOUND | | TRANSMISSION REQUIREMENTS, AS WELL AS, FLAME SPREAD AND | | SMOKE DEVELOPED REQUIREMENTS OF FBC SECTIONS 603 AND | | 805. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|