2014-08-30 07:33:22 | BUILDING PLAN REVIEW |
| PERMIT: 14050928 |
| ADD: 2420 FLORIDA AVENUE |
| CONT: K & M COMMERCIAL CONSTRUCTION |
| TEL: (561)383-2817 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: SAT. AUG. 30/ 2014 |
| ACTION: DENIED |
| |
| NOTE THIS REVIEW WILL BE BASED ON THE 2010 FL. EXISITNG |
| BUILDING CODE SECTION 901.3 CHANGE OF OCCUPANCY |
| CLASSIFICATION. |
| WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912 |
| SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| GROUP. |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1) COVER SHEET CODE INFORMATION: |
| 1A)(1) THIS SHEET LIST F1, S2 & B OCCUPANCNCIES AS |
| NON--SEPARATED OCCUPANCIES. |
| PLEASE PROVIDE A BREAK DOWN IN SQUARE FEET FOR EACH OF |
| THE OCCUPANCY GROUPS. 2010 FBC-B 508.3.2 ALLOWABLE |
| BUILDING AREA AND HEIGHT. |
| THE ALLOWABLE BUILDING AREA AND HEIGHT OF THE BUILDING |
| OR PORTION THEREOF SHALL BE BASED ON THE MOST |
| RESTRICTIVE ALLOWANCES FOR THE OCCUPANCY GROUPS UNDER |
| CONSIDERATION FOR THE TYPE OF CONSTRUCTION OF THE |
| BUILDING IN ACCORDANCE WITH SECTION 503.1. |
| |
| 1A)(2) PLEASE PROVIDE THE TYPE OF INVENTORY THAT WILL |
| BE STORED IN THE S2 STORAGE OCCUPANCY, THE USAGE AND |
| MATERIALS STORED WOULD APPEAR TO MAKE THIS A S1 TYPE |
| OCCUPANCY. 2010 FBC-B 311.2 MODERATE-HAZARD STORAGE |
| S-1. PLEASE PROVIDE THE INVENTORY OF STORAGE ON THE |
| PLANS FOR DOCUMENTATION. 107.2.1.4 QUALITY OF BUILDING |
| PLANS.THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| SPECIFICATIONS, FOR THE RECORD RETENTION PROGRAM. |
| |
| 1B) THE DECLARED NONSEPARATED OCCUPANCIES PLEASE REVIEW |
| FBC-B 508.3.1 AND 508.3.2 FOR THE LIMITING FACTOR IN |
| NONSEPATED OCCUPANCIES. IN FBC-B 508.3.1 CHAPTER 9 |
| SECTION: |
| 903.2.4 (1) A GROUP F-1 FIRE AREA EXCEEDS 12,000 SQUARE |
| FEET (1115 M2) WILL REQUIRE FIRE SPRINKLERS. |
| 903.2.9 GROUP S-1. AN AUTOMATIC SPRINKLER SYSTEM SHALL |
| BE PROVIDED THROUGHOUT ALL BUILDINGS CONTAINING A GROUP |
| S-1 OCCUPANCY WHERE ONE OF THE FOLLOWING CONDITIONS |
| EXISTS:(1.) A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE |
| FEET (1115 M2). |
| |
| 1C) FBC-B 508.3.2 DEALS WIH THE ALLOWABLE BUILDING AREA |
| AND HEIGHT OF THE BUILDING OR PORTION THEREOF SHALL BE |
| BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE |
| OCCUPANCY GROUPS UNDER CONSIDERATION FOR THE TYPE OF |
| CONSTRUCTION OF THE BUILDING. 2010 FBC-B TABLE 503 WILL |
| ONLY ALLOW 15,500 SQ FT FOR A F1 OCCUPANCY |
| NON-SPRINKLERED.ALSO REVIEW 508.2.3. CORRECT NOTE FOUND |
| ON THE COVRE SHEET & SHEET A1.3 ALLOWABLE HEIGHT AND |
| AREA. WHERE AN OPEN AREA EXCEEDS 30 FT, YOU CAN ONLY |
| TAKE 30 FT OR TTHE MULTIPLIER BECOMES A 1 IN THIS CASE. |
| 15,500 + 11,625= 27,125 SQ FT. |
| |
| |
| 2) SEMI-COMPLIED. WALK -IN COOLERS ARE TO BE FIRE |
| SPRINKLERED TO SATISFY CODE REQUIREMENT 2603.4.1.3 |
| ALLOWABLE AREA FOR NON-SPRINKLERED WALK IN COOLERS. WE |
| WILL NEED A ENGINEERED PLAN (IF OVER 50 SPRINKLER |
| HEADS, OTHERWISE A CONTRACTOR CAN DESIGN) FLOW TEST AND |
| SPECIFICATIONS. FOR THE REQUIRED FIRE SPRINKLER PLANS |
| THE HYDROLICS AND SHOP DRAWING ARE REQUIRED. ALSO SEE |
| FIRE COMMENS FOR REQUIRED DESIGN. |
| 903.1.1 ALTERNATIVE PROTECTION. |
| ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS |
| COMPLYING WITH SECTION 904 SHALL BE PERMITTED IN LIEU |
| OF AUTOMATIC SPRINKLER PROTECTION WHERE RECOGNIZED BY |
| THE APPLICABLE STANDARD AND APPROVED BY THE FIRE CODE |
| OFFICIAL. |
| |
| |
| 1ST ROUND REVIEW COMMENT. SHEET A1.2 INDICATES NEW FOAM |
| INSULATION IN WALK IN COOLERS PLEASE REVIEW 2603.4.1.3 |
| 2010 FBC-B SECTION FOR ALLOWABLE AREA FOR WALK IN |
| COOLERS NON-SPRINKLERED BUILDINGS. |
| FBC-B 2603.4.1.3 WALK-IN COOLERS. IN NONSPRINKLERED |
| BUILDINGS, FOAM PLASTIC HAVING A THICKNESS THAT DOES |
| NOT EXCEED 4 INCHES (102 MM) AND A MAXIMUM FLAME SPREAD |
| INDEX OF 75 IS PERMITTED IN WALK-IN COOLERS OR FREEZER |
| UNITS WHERE THE AGGREGATE FLOOR AREA DOES NOT EXCEED |
| 400 SQUARE FEET (37 M2) AND THE FOAM PLASTIC IS COVERED |
| BY A METAL FACING NOT LESS THAN 0.032-INCH-THICK (0.81 |
| MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A |
| MINIMUM BASE METAL THICKNESS OF 0.016 INCH (0.41 MM). A |
| THICKNESS OF UP TO 10 INCHES (254 MM) IS PERMITTED |
| WHERE PROTECTED BY A THERMAL BARRIER. |
| |
| 3) SHEET A1.3 LIFE SAFETY SHEET: |
| |
| 3A) COMPLIED. THIS SHEET INDICATES THE 12,290 SQ FT |
| AREA F2 OCCUPANCY BUT MAKES REFERANCE TO 1004.1 |
| EXCEPTION # 1 IN A SPECIAL PURPOSE FACTORY-INDUSTRIAL |
| OCCUPANCY, THE OCCUPANT LOAD SHALL BE THE MAXIMUM |
| NUMBER OF PERSONS TO OCCUPY THE AREA UNDER ANY PROBABLE |
| CONDITIONS AS THE LIMITING THE OCCUPANT LOAD TO 40 |
| OCCUPANTS. PLEASE NOTE THE BUILDING OFFICIAL HAS |
| REVIEWED AND DECLARED THIS TO BE A F1 TYPE OCCUPANCY. |
| THE MAKING REFERANCE TO THE SPECIAL PURPOSE |
| FACTORY-INDUSTRIAL OCCUPANCY YOU ARE NOW DECLARING THIS |
| TO BE A F3 TYPE OCCUCANCY SINCE THIS IS WHERE SPECIAL |
| PURPOSE FACTORY-INDUCTRIAL REFERANCE OCCURS SEE 306.4 |
| SPECIAL PURPOSE F-3. |
| THE 2010 FBC-B TABLE 1004.1.1 DECLARES THE OCCUPANCY TO |
| BE FIGURED AT 100 SQ FT/ OCCUPANT OR 123 OCCUPANTS FOR |
| THIS AREA. |
| THE 2010 FBC-B TABLE 1015. 1 ONLY ALLOWS 49 OCCUPANTS |
| WITH A SINGLE EXIT. FBC-B TABLE 1016.1 WILL ONLY ALLOW |
| 200 FT IN A F1 TYPE OCCUPANCY. THIS AREA WILL REQUIRE 2 |
| EXITS FROM THIS LOCATION 1015.2 EXIT OR EXIT ACCESS |
| DOORWAY ARRANGEMENT |
| |
| 3B) COMPLIED. |
| |
| 3C)COMPLIED. PLEASE UPDATE THE OCCUPANT LOADS TO |
| REFLECT THE F1 OCCUPANCY THIS MAY EFFECT THE REQUIRED |
| FIXTURE COUNT REQUIRED UNDER THE PLUMBING CODE. |
| |
| 4) COVERSHEET SHOWS A NEW ALUMINUM SHADE CANOPY PLEASE |
| PROVIDE THE SQUARE FEET OF AREA THIS WILL COVER AND |
| SHOW ALSO ON THE A-1 SHEET NOT SURE IF ONLY THE LOADING |
| DOCK OR IF THE CANOPY WILL GO ALLTHE WAY BACK TO THE |
| EXISTING LOADING DOCK? CANOPY TO BE UNDER A SEPARATE |
| PERMIT. |
| |
| 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |