Plan Review Notes
Plan Review Notes For Permit 14050928
Permit Number 14050928
Review Stop B
Sequence Number 2
Notes
Date Text
2014-08-30 07:33:22BUILDING PLAN REVIEW
 PERMIT: 14050928
 ADD: 2420 FLORIDA AVENUE
 CONT: K & M COMMERCIAL CONSTRUCTION
 TEL: (561)383-2817
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. AUG. 30/ 2014
 ACTION: DENIED
  
 NOTE THIS REVIEW WILL BE BASED ON THE 2010 FL. EXISITNG
 BUILDING CODE SECTION 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1) COVER SHEET CODE INFORMATION:
 1A)(1) THIS SHEET LIST F1, S2 & B OCCUPANCNCIES AS
 NON--SEPARATED OCCUPANCIES.
 PLEASE PROVIDE A BREAK DOWN IN SQUARE FEET FOR EACH OF
 THE OCCUPANCY GROUPS. 2010 FBC-B 508.3.2 ALLOWABLE
 BUILDING AREA AND HEIGHT.
 THE ALLOWABLE BUILDING AREA AND HEIGHT OF THE BUILDING
 OR PORTION THEREOF SHALL BE BASED ON THE MOST
 RESTRICTIVE ALLOWANCES FOR THE OCCUPANCY GROUPS UNDER
 CONSIDERATION FOR THE TYPE OF CONSTRUCTION OF THE
 BUILDING IN ACCORDANCE WITH SECTION 503.1.
  
 1A)(2) PLEASE PROVIDE THE TYPE OF INVENTORY THAT WILL
 BE STORED IN THE S2 STORAGE OCCUPANCY, THE USAGE AND
 MATERIALS STORED WOULD APPEAR TO MAKE THIS A S1 TYPE
 OCCUPANCY. 2010 FBC-B 311.2 MODERATE-HAZARD STORAGE
 S-1. PLEASE PROVIDE THE INVENTORY OF STORAGE ON THE
 PLANS FOR DOCUMENTATION. 107.2.1.4 QUALITY OF BUILDING
 PLANS.THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, FOR THE RECORD RETENTION PROGRAM.
  
 1B) THE DECLARED NONSEPARATED OCCUPANCIES PLEASE REVIEW
 FBC-B 508.3.1 AND 508.3.2 FOR THE LIMITING FACTOR IN
 NONSEPATED OCCUPANCIES. IN FBC-B 508.3.1 CHAPTER 9
 SECTION:
 903.2.4 (1) A GROUP F-1 FIRE AREA EXCEEDS 12,000 SQUARE
 FEET (1115 M2) WILL REQUIRE FIRE SPRINKLERS.
 903.2.9 GROUP S-1. AN AUTOMATIC SPRINKLER SYSTEM SHALL
 BE PROVIDED THROUGHOUT ALL BUILDINGS CONTAINING A GROUP
 S-1 OCCUPANCY WHERE ONE OF THE FOLLOWING CONDITIONS
 EXISTS:(1.) A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE
 FEET (1115 M2).
  
 1C) FBC-B 508.3.2 DEALS WIH THE ALLOWABLE BUILDING AREA
 AND HEIGHT OF THE BUILDING OR PORTION THEREOF SHALL BE
 BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE
 OCCUPANCY GROUPS UNDER CONSIDERATION FOR THE TYPE OF
 CONSTRUCTION OF THE BUILDING. 2010 FBC-B TABLE 503 WILL
 ONLY ALLOW 15,500 SQ FT FOR A F1 OCCUPANCY
 NON-SPRINKLERED.ALSO REVIEW 508.2.3. CORRECT NOTE FOUND
 ON THE COVRE SHEET & SHEET A1.3 ALLOWABLE HEIGHT AND
 AREA. WHERE AN OPEN AREA EXCEEDS 30 FT, YOU CAN ONLY
 TAKE 30 FT OR TTHE MULTIPLIER BECOMES A 1 IN THIS CASE.
 15,500 + 11,625= 27,125 SQ FT.
  
  
 2) SEMI-COMPLIED. WALK -IN COOLERS ARE TO BE FIRE
 SPRINKLERED TO SATISFY CODE REQUIREMENT 2603.4.1.3
 ALLOWABLE AREA FOR NON-SPRINKLERED WALK IN COOLERS. WE
 WILL NEED A ENGINEERED PLAN (IF OVER 50 SPRINKLER
 HEADS, OTHERWISE A CONTRACTOR CAN DESIGN) FLOW TEST AND
 SPECIFICATIONS. FOR THE REQUIRED FIRE SPRINKLER PLANS
 THE HYDROLICS AND SHOP DRAWING ARE REQUIRED. ALSO SEE
 FIRE COMMENS FOR REQUIRED DESIGN.
 903.1.1 ALTERNATIVE PROTECTION.
 ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS
 COMPLYING WITH SECTION 904 SHALL BE PERMITTED IN LIEU
 OF AUTOMATIC SPRINKLER PROTECTION WHERE RECOGNIZED BY
 THE APPLICABLE STANDARD AND APPROVED BY THE FIRE CODE
 OFFICIAL.
  
  
 1ST ROUND REVIEW COMMENT. SHEET A1.2 INDICATES NEW FOAM
 INSULATION IN WALK IN COOLERS PLEASE REVIEW 2603.4.1.3
 2010 FBC-B SECTION FOR ALLOWABLE AREA FOR WALK IN
 COOLERS NON-SPRINKLERED BUILDINGS.
 FBC-B 2603.4.1.3 WALK-IN COOLERS. IN NONSPRINKLERED
 BUILDINGS, FOAM PLASTIC HAVING A THICKNESS THAT DOES
 NOT EXCEED 4 INCHES (102 MM) AND A MAXIMUM FLAME SPREAD
 INDEX OF 75 IS PERMITTED IN WALK-IN COOLERS OR FREEZER
 UNITS WHERE THE AGGREGATE FLOOR AREA DOES NOT EXCEED
 400 SQUARE FEET (37 M2) AND THE FOAM PLASTIC IS COVERED
 BY A METAL FACING NOT LESS THAN 0.032-INCH-THICK (0.81
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A
 MINIMUM BASE METAL THICKNESS OF 0.016 INCH (0.41 MM). A
 THICKNESS OF UP TO 10 INCHES (254 MM) IS PERMITTED
 WHERE PROTECTED BY A THERMAL BARRIER.
  
 3) SHEET A1.3 LIFE SAFETY SHEET:
  
 3A) COMPLIED. THIS SHEET INDICATES THE 12,290 SQ FT
 AREA F2 OCCUPANCY BUT MAKES REFERANCE TO 1004.1
 EXCEPTION # 1 IN A SPECIAL PURPOSE FACTORY-INDUSTRIAL
 OCCUPANCY, THE OCCUPANT LOAD SHALL BE THE MAXIMUM
 NUMBER OF PERSONS TO OCCUPY THE AREA UNDER ANY PROBABLE
 CONDITIONS AS THE LIMITING THE OCCUPANT LOAD TO 40
 OCCUPANTS. PLEASE NOTE THE BUILDING OFFICIAL HAS
 REVIEWED AND DECLARED THIS TO BE A F1 TYPE OCCUPANCY.
 THE MAKING REFERANCE TO THE SPECIAL PURPOSE
 FACTORY-INDUSTRIAL OCCUPANCY YOU ARE NOW DECLARING THIS
 TO BE A F3 TYPE OCCUCANCY SINCE THIS IS WHERE SPECIAL
 PURPOSE FACTORY-INDUCTRIAL REFERANCE OCCURS SEE 306.4
 SPECIAL PURPOSE F-3.
 THE 2010 FBC-B TABLE 1004.1.1 DECLARES THE OCCUPANCY TO
 BE FIGURED AT 100 SQ FT/ OCCUPANT OR 123 OCCUPANTS FOR
 THIS AREA.
 THE 2010 FBC-B TABLE 1015. 1 ONLY ALLOWS 49 OCCUPANTS
 WITH A SINGLE EXIT. FBC-B TABLE 1016.1 WILL ONLY ALLOW
 200 FT IN A F1 TYPE OCCUPANCY. THIS AREA WILL REQUIRE 2
 EXITS FROM THIS LOCATION 1015.2 EXIT OR EXIT ACCESS
 DOORWAY ARRANGEMENT
  
 3B) COMPLIED.
  
 3C)COMPLIED. PLEASE UPDATE THE OCCUPANT LOADS TO
 REFLECT THE F1 OCCUPANCY THIS MAY EFFECT THE REQUIRED
 FIXTURE COUNT REQUIRED UNDER THE PLUMBING CODE.
  
 4) COVERSHEET SHOWS A NEW ALUMINUM SHADE CANOPY PLEASE
 PROVIDE THE SQUARE FEET OF AREA THIS WILL COVER AND
 SHOW ALSO ON THE A-1 SHEET NOT SURE IF ONLY THE LOADING
 DOCK OR IF THE CANOPY WILL GO ALLTHE WAY BACK TO THE
 EXISTING LOADING DOCK? CANOPY TO BE UNDER A SEPARATE
 PERMIT.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO