2014-06-25 18:40:36 | BUILDING PLAN REVIEW |
| PERMIT: 14050928 |
| ADD: 2420 FLORIDA AVENUE |
| CONT: K & M COMMERCIAL CONSTRUCTION |
| TEL: (561)383-2817 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JUNE 25/ 2014 |
| ACTION: DENIED |
| |
| NOTE THIS REVIEW WILL BE BASED ON THE 2010 FL. EXISITNG |
| BUILDING CODE SECTION 901.3 CHANGE OF OCCUPANCY |
| CLASSIFICATION. |
| WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912 |
| SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF |
| OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT |
| GROUP. |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1) COVER SHEET CODE INFORMATION: |
| 1A) THIS SHEET LIST F2, S2 & B OCCUPANCNCIES AS |
| UN-SEPARATED USE. |
| THE FIRST ISSUE IS THE DECLARED F2 OCCUPANCY (12,290 SQ |
| FT AREA), THE BUILDING OFFICIAL HAS REVIEWED THE |
| PROJECT WITH ME AND HE HAS DETERMINED THIS AREA TO BE |
| CONSIDERED A F1 OCCUPANCY. THE F2 OCCUPANCIES INCLUDED |
| BRICK, CERAMIC PRODUCTS, FOUNDRIES GYPSUM PRODUCTS |
| ETC... 2010 FBC-B 306.2 |
| |
| 1B) THE DECLARED NONSEPARATED OCCUPANCIES PLEASE REVIEW |
| FBC-B 508.3.1 AND 508.3.2 FOR THE LIMITING FACTOR IN |
| NONSEPATED OCCUPANCIES. IN FBC-B 508.3.1 CHAPTER 9 |
| SECTION 903.2.4 (1) A GROUP F-1 FIRE AREA EXCEEDS |
| 12,000 SQUARE FEET (1115 M2) WILL REQUIRE FIRE |
| SPRINKLERS. |
| |
| 1C) FBC-B 508.3.2 DEALS WIH THE ALLOWABLE BUILDING AREA |
| AND HEIGHT OF THE BUILDING OR PORTION THEREOF SHALL BE |
| BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE |
| OCCUPANCY GROUPS UNDER CONSIDERATION FOR THE TYPE OF |
| CONSTRUCTION OF THE BUILDING. 2010 FBC-B TABLE 503 WILL |
| ONLY ALLOW 12,000 SQ FT FOR A F1 OCCUPANCY |
| NON-SPRINKLERED.ALSO REVIEW 508.2.3. CORRECT NOTE FOUND |
| ON SHEET A1.3 ALLOWABLE HEIGHT AND AREA. |
| |
| 2) SHEET A1.2 INDICATES NEW FOAM INSULATION IN WALK IN |
| COOLERS PLEASE REVIEW 2603.4.1.3 2010 FBC-B SECTION FOR |
| ALLOWABLE AREA FOR WALK IN COOLERS NON-SPRINKLERED |
| BUILDINGS. |
| FBC-B 2603.4.1.3 WALK-IN COOLERS. IN NONSPRINKLERED |
| BUILDINGS, FOAM PLASTIC HAVING A THICKNESS THAT DOES |
| NOT EXCEED 4 INCHES (102 MM) AND A MAXIMUM FLAME SPREAD |
| INDEX OF 75 IS PERMITTED IN WALK-IN COOLERS OR FREEZER |
| UNITS WHERE THE AGGREGATE FLOOR AREA DOES NOT EXCEED |
| 400 SQUARE FEET (37 M2) AND THE FOAM PLASTIC IS COVERED |
| BY A METAL FACING NOT LESS THAN 0.032-INCH-THICK (0.81 |
| MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A |
| MINIMUM BASE METAL THICKNESS OF 0.016 INCH (0.41 MM). A |
| THICKNESS OF UP TO 10 INCHES (254 MM) IS PERMITTED |
| WHERE PROTECTED BY A THERMAL BARRIER. |
| |
| 3) SHEET A1.3 LIFE SAFETY SHEET: |
| |
| 3A) THIS SHEET INDICATES THE 12,290 SQ FT AREA F2 |
| OCCUPANCY BUT MAKES REFERANCE TO 1004.1 EXCEPTION # 1 |
| IN A SPECIAL PURPOSE FACTORY-INDUSTRIAL OCCUPANCY, THE |
| OCCUPANT LOAD SHALL BE THE MAXIMUM NUMBER OF PERSONS TO |
| OCCUPY THE AREA UNDER ANY PROBABLE CONDITIONS AS THE |
| LIMITING THE OCCUPANT LOAD TO 40 OCCUPANTS. PLEASE NOTE |
| THE BUILDING OFFICIAL HAS REVIEWED AND DECLARED THIS TO |
| BE A F1 TYPE OCCUPANCY. THE MAKING REFERANCE TO THE |
| SPECIAL PURPOSE FACTORY-INDUSTRIAL OCCUPANCY YOU ARE |
| NOW DECLARING THIS TO BE A F3 TYPE OCCUCANCY SINCE THIS |
| IS WHERE SPECIAL PURPOSE FACTORY-INDUCTRIAL REFERANCE |
| OCCURS SEE 306.4 SPECIAL PURPOSE F-3. |
| THE 2010 FBC-B TABLE 1004.1.1 DECLARES THE OCCUPANCY TO |
| BE FIGURED AT 100 SQ FT/ OCCUPANT OR 123 OCCUPANTS FOR |
| THIS AREA. |
| THE 2010 FBC-B TABLE 1015. 1 ONLY ALLOWS 49 OCCUPANTS |
| WITH A SINGLE EXIT. FBC-B TABLE 1016.1 WILL ONLY ALLOW |
| 200 FT IN A F1 TYPE OCCUPANCY. THIS AREA WILL REQUIRE 2 |
| EXITS FROM THIS LOCATION 1015.2 EXIT OR EXIT ACCESS |
| DOORWAY ARRANGEMENT |
| |
| 3B) 1015.5 REFRIGERATED ROOMS OR SPACES. |
| ROOMS OR SPACES HAVING A FLOOR AREA LARGER THAN 1,000 |
| SQUARE FEET (93 M2), CONTAINING A REFRIGERANT |
| EVAPORATOR AND MAINTAINED AT A TEMPERATURE BELOW 68?F |
| (20?C), SHALL HAVE ACCESS TO NOT LESS THAN TWO EXITS OR |
| EXIT ACCESS DOORS. |
| |
| TRAVEL DISTANCE SHALL BE DETERMINED AS SPECIFIED IN |
| SECTION 1016.1, BUT ALL PORTIONS OF A REFRIGERATED ROOM |
| OR SPACE SHALL BE WITHIN 150 FEET (45 720 MM) OF AN |
| EXIT OR EXIT ACCESS DOOR WHERE SUCH ROOMS ARE NOT |
| PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM. |
| EGRESS IS ALLOWED THROUGH ADJOINING REFRIGERATED ROOMS |
| OR SPACES. |
| |
| 3C) PLEASE UPDATE THE OCCUPANT LOADS TO REFLECT THE F1 |
| OCCUPANCY THIS MAY EFFECT THE REQUIRED FIXTURE COUNT |
| REQUIRED UNDER THE PLUMBING CODE. |
| |
| 4) |
| |
| |
| |
| |
| |
| |
| |