Plan Review Notes
Plan Review Notes For Permit 14050928
Permit Number 14050928
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-25 18:40:36BUILDING PLAN REVIEW
 PERMIT: 14050928
 ADD: 2420 FLORIDA AVENUE
 CONT: K & M COMMERCIAL CONSTRUCTION
 TEL: (561)383-2817
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 25/ 2014
 ACTION: DENIED
  
 NOTE THIS REVIEW WILL BE BASED ON THE 2010 FL. EXISITNG
 BUILDING CODE SECTION 901.3 CHANGE OF OCCUPANCY
 CLASSIFICATION.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 902 THROUGH 912
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION WITHIN A GROUP AS WELL AS A CHANGE OF
 OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A DIFFERENT
 GROUP.
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1) COVER SHEET CODE INFORMATION:
 1A) THIS SHEET LIST F2, S2 & B OCCUPANCNCIES AS
 UN-SEPARATED USE.
 THE FIRST ISSUE IS THE DECLARED F2 OCCUPANCY (12,290 SQ
 FT AREA), THE BUILDING OFFICIAL HAS REVIEWED THE
 PROJECT WITH ME AND HE HAS DETERMINED THIS AREA TO BE
 CONSIDERED A F1 OCCUPANCY. THE F2 OCCUPANCIES INCLUDED
 BRICK, CERAMIC PRODUCTS, FOUNDRIES GYPSUM PRODUCTS
 ETC... 2010 FBC-B 306.2
  
 1B) THE DECLARED NONSEPARATED OCCUPANCIES PLEASE REVIEW
 FBC-B 508.3.1 AND 508.3.2 FOR THE LIMITING FACTOR IN
 NONSEPATED OCCUPANCIES. IN FBC-B 508.3.1 CHAPTER 9
 SECTION 903.2.4 (1) A GROUP F-1 FIRE AREA EXCEEDS
 12,000 SQUARE FEET (1115 M2) WILL REQUIRE FIRE
 SPRINKLERS.
  
 1C) FBC-B 508.3.2 DEALS WIH THE ALLOWABLE BUILDING AREA
 AND HEIGHT OF THE BUILDING OR PORTION THEREOF SHALL BE
 BASED ON THE MOST RESTRICTIVE ALLOWANCES FOR THE
 OCCUPANCY GROUPS UNDER CONSIDERATION FOR THE TYPE OF
 CONSTRUCTION OF THE BUILDING. 2010 FBC-B TABLE 503 WILL
 ONLY ALLOW 12,000 SQ FT FOR A F1 OCCUPANCY
 NON-SPRINKLERED.ALSO REVIEW 508.2.3. CORRECT NOTE FOUND
 ON SHEET A1.3 ALLOWABLE HEIGHT AND AREA.
  
 2) SHEET A1.2 INDICATES NEW FOAM INSULATION IN WALK IN
 COOLERS PLEASE REVIEW 2603.4.1.3 2010 FBC-B SECTION FOR
 ALLOWABLE AREA FOR WALK IN COOLERS NON-SPRINKLERED
 BUILDINGS.
 FBC-B 2603.4.1.3 WALK-IN COOLERS. IN NONSPRINKLERED
 BUILDINGS, FOAM PLASTIC HAVING A THICKNESS THAT DOES
 NOT EXCEED 4 INCHES (102 MM) AND A MAXIMUM FLAME SPREAD
 INDEX OF 75 IS PERMITTED IN WALK-IN COOLERS OR FREEZER
 UNITS WHERE THE AGGREGATE FLOOR AREA DOES NOT EXCEED
 400 SQUARE FEET (37 M2) AND THE FOAM PLASTIC IS COVERED
 BY A METAL FACING NOT LESS THAN 0.032-INCH-THICK (0.81
 MM) ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A
 MINIMUM BASE METAL THICKNESS OF 0.016 INCH (0.41 MM). A
 THICKNESS OF UP TO 10 INCHES (254 MM) IS PERMITTED
 WHERE PROTECTED BY A THERMAL BARRIER.
  
 3) SHEET A1.3 LIFE SAFETY SHEET:
  
 3A) THIS SHEET INDICATES THE 12,290 SQ FT AREA F2
 OCCUPANCY BUT MAKES REFERANCE TO 1004.1 EXCEPTION # 1
 IN A SPECIAL PURPOSE FACTORY-INDUSTRIAL OCCUPANCY, THE
 OCCUPANT LOAD SHALL BE THE MAXIMUM NUMBER OF PERSONS TO
 OCCUPY THE AREA UNDER ANY PROBABLE CONDITIONS AS THE
 LIMITING THE OCCUPANT LOAD TO 40 OCCUPANTS. PLEASE NOTE
 THE BUILDING OFFICIAL HAS REVIEWED AND DECLARED THIS TO
 BE A F1 TYPE OCCUPANCY. THE MAKING REFERANCE TO THE
 SPECIAL PURPOSE FACTORY-INDUSTRIAL OCCUPANCY YOU ARE
 NOW DECLARING THIS TO BE A F3 TYPE OCCUCANCY SINCE THIS
 IS WHERE SPECIAL PURPOSE FACTORY-INDUCTRIAL REFERANCE
 OCCURS SEE 306.4 SPECIAL PURPOSE F-3.
 THE 2010 FBC-B TABLE 1004.1.1 DECLARES THE OCCUPANCY TO
 BE FIGURED AT 100 SQ FT/ OCCUPANT OR 123 OCCUPANTS FOR
 THIS AREA.
 THE 2010 FBC-B TABLE 1015. 1 ONLY ALLOWS 49 OCCUPANTS
 WITH A SINGLE EXIT. FBC-B TABLE 1016.1 WILL ONLY ALLOW
 200 FT IN A F1 TYPE OCCUPANCY. THIS AREA WILL REQUIRE 2
 EXITS FROM THIS LOCATION 1015.2 EXIT OR EXIT ACCESS
 DOORWAY ARRANGEMENT
  
 3B) 1015.5 REFRIGERATED ROOMS OR SPACES.
 ROOMS OR SPACES HAVING A FLOOR AREA LARGER THAN 1,000
 SQUARE FEET (93 M2), CONTAINING A REFRIGERANT
 EVAPORATOR AND MAINTAINED AT A TEMPERATURE BELOW 68?F
 (20?C), SHALL HAVE ACCESS TO NOT LESS THAN TWO EXITS OR
 EXIT ACCESS DOORS.
  
 TRAVEL DISTANCE SHALL BE DETERMINED AS SPECIFIED IN
 SECTION 1016.1, BUT ALL PORTIONS OF A REFRIGERATED ROOM
 OR SPACE SHALL BE WITHIN 150 FEET (45 720 MM) OF AN
 EXIT OR EXIT ACCESS DOOR WHERE SUCH ROOMS ARE NOT
 PROTECTED BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM.
 EGRESS IS ALLOWED THROUGH ADJOINING REFRIGERATED ROOMS
 OR SPACES.
  
 3C) PLEASE UPDATE THE OCCUPANT LOADS TO REFLECT THE F1
 OCCUPANCY THIS MAY EFFECT THE REQUIRED FIXTURE COUNT
 REQUIRED UNDER THE PLUMBING CODE.
  
 4)
  
  
  
  
  
  
  