2014-05-29 10:20:49 | ELECTRICAL DENIED BASED ON THE 2008 EDITION OF THE NEC | | AND THE 2010 EDITION OF THE FLORIDA BUILDING CODE | | | | 1) PROVIDE SMOKE DETECTORS AS REQUIRED FOR NEW | | DWELLINGS. FBC-R 314.3.1, 315.1, FBC 107.3.5 | | | | 2) RECESSED LUMINAIRES SHALL BE SEALED, AIR TIGHT AND | | IC RATED. FBC 402.4.5 | | | | 3) ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC | | 406.8(B) | | | | 4) THOSE OUTLETS IN WET LOCATIONS SHALL BE GFI & | | WEATHER RESISTANT. NEC 406.11 | | | | 5) ALL OUTLETS REQUIRING GFI PROTECTION SHALL MEET THE | | PROVISIONS OF NEC 210.8 | | | | 6) ALL OUTLETS REQUIRING ARC FAULT PROTECTION SHALL | | MEET THE PROVISIONS OF NEC 210.12 | | | | 7) THE MINIMUM OUTLET REQUIREMENTS FOR DWELLING UNITS | | SHALL MEET THE PROVISIONS OF NEC 210.52 | | | | 8) GROUNDING ELECTRODE SYSTEM SHALL MEET THE PROVISIONS | | OF NEC 250 | | | | 9) SERVICE DISCONNECTING MEANS SHALL BE PROVIDED. NEC | | 230.70 | | | | 10) ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT AND | | GROUNDING DETAIL, AND PANEL SCHEDULE REQUIRED. FBC- | | 107.3.5.3 ? | | | | 11) LUMINAIRES IN CLOTHES CLOSETS SHALL MEET THE | | PROVISIONS OF NEC 410.16 | | | | 12) PERSON RESPONSIBLE FOR THE ELECTRICAL DESIGN TO | | PROVIDE NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 | | CITY AMENDMENTS. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR AT [email protected] | | | | | | | | |
|