2014-08-04 15:16:46 | BUILDING PLAN REVIEW |
| PERMIT: 14050913 |
| ADD: 1016 CLARE SUITE # 3 |
| CONT: RIELLY CONSTRUCTION |
| TEL: (561)262-6876 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MONDAY JUNE 23/ 2014 |
| ACTION: DENIED |
| |
| 1) THE LIFE SAFETY SHEET LS 1.1 DESIGN STANDARDS & CODE |
| REQUIREMENT HEADING LIST THE BUILDING AS FULLY |
| SPRINKLERED WITH A NFPA 13 SYSTEM. PLEASE NOTE THAT THE |
| SPRINKLERS DOES NOT STATE WHAT TYPE OF HEADS ARE |
| CURRENTLY IN USE. PLEASE REFER TO THE 2010 FBC-B |
| SECTION 709.1 EXCEPTION #3 THAT WILL GREATLY EFFECT |
| YOUR DESIGN AND CODE COMPLIANCE. EXCEPTION 3. IN |
| MINI-WAREHOUSES/SELF-STORAGE BUILDINGS, WALLS USED TO |
| SEPARATE TENANTS SHALL NOT BE REQUIRED TO HAVE |
| FIRE-RESISTANCE RATING, PROVIDED A SPRINKLER SYSTEM |
| MEETING THE REQUIREMENTS OF ORDINARY HAZARD GROUP II AS |
| DEFINED BY NFPA 13, IS INSTALLED EMPLOYING QUICK |
| RESPONSE HEADS. |
| |
| 2) COMPLIED. |
| |
| 3) 2ND REVIEW, RESPONSE INDICATES THE CONTRACTOR WILL |
| PROVIDE A COST BREAKDOWN OF THE EXPENDITURES ON |
| ACCISSIBILITY AND ACCESSIBLE ITEMS. NO SUCHDOCUMENTS |
| WERE SUBMITTED FOR THIS REVIEW. |
| LS1.1 PLEASE PROVIDE A COST BREAK DOWN WHERE 20% OR |
| $70.00 DOLLARS IN ACCESSIBLE UPGRADES TO THE BUILDING. |
| 2010 FL ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES |
| IN THE EVENT OF DISPROPORTIONALITY. |
| WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| ALARMS. |
| |
| |
| 4A) PROVISO SHOP DRAWINGS TO FOLLOW< DEFERRED |
| SUBMITTAL; THE PLANS INDICATE A NEW ELEVATOR, THIS |
| ELEVATOR WILL NEED TO COMPLY WITH THE 2010 |
| FBC-ACCESSIBILITY CODE 3001.3 ACCESSIBILITY. |
| PASSENGER ELEVATORS ARE REQUIRED TO BE ACCESSIBLE BY |
| THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| |
| 4B) PROVISO SHOP DRAWINGS TO FOLLOW< DEFERRED |
| SUBMITTAL. NEW WORK. 2010 FBC-B 3001.5.1 EACH NEW |
| ELEVATOR SHALL COMPLY WITH THE FLORIDA ELEVATOR SAFETY |
| CODE THAT WAS IN EFFECT AT THE TIME OF RECEIPT OF |
| APPLICATION FOR THE CONSTRUCTION PERMIT FOR THE |
| ELEVATOR. NO SUBMITTALS FOR EITHER THE FREIGHT |
| ELEVATOR. |
| |
| 5) SEMI-COMPLIED. THE PLANS SHOW A 1 HOUR RATED WALL ON |
| THE 1ST FLOOR MISSING ON LS 1.2. 3002.1.1 OPENING |
| PROTECTIVES. OPENINGS IN HOISTWAY ENCLOSURES SHALL BE |
| PROTECTED AS REQUIRED IN CHAPTER 7. DOORS ARE (1) HOUR |
| FIRE RATED NOT SHOWN ON PLANS. |
| |
| 6-9) COMPLIED. |
| |
| 10) SINCE THIS BUILDING IS CHANGING THE USAGE TYPE FROM |
| STORAGE TO MINI STORAGE UNITS TTHE PLANS WILL NEED TO |
| GO TO P B C IMPACT FEE OFFICE FOR ASSESSMENT OF IMPACT |
| FEES. |
| |
| 11) NEW COMMENT, SHEET LS2 NOT CHANGED OUT SHOWING THE |
| LULA LIFT TO THE 2ND FLOOR NOR THE REQUIRED 1 HOUR |
| ENCLOSURE AND DOOR. |
| |
| 12) NEW COMMENT SHEETS S-2 & S3 HAVE NOT BEEN UPDATED |
| TO SHOW THE LULA LIFT PENETRATING THE 2ND FLOOR AND |
| STEEL FRAMING MEMBERS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |