2014-06-23 07:48:15 | BUILDING PLAN REVIEW |
| PERMIT: 14050913 |
| ADD: 1016 CLARE SUITE # 3 |
| CONT: RIELLY CONSTRUCTION |
| TEL: (561)262-6876 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MONDAY JUNE 23/ 2014 |
| ACTION: DENIED |
| |
| 1) THE LIFE SAFETY SHEET LS 1.1 DESIGN STANDAARDS & |
| CODE REQUIREMENT HEADING LIST THE BUILDING AS FULLY |
| SPRINKLERED WITH A NFPA 13 SYSTEM. PLEASE NOTE THAT THE |
| SPRINKLERS DOES NOT STATE WHAT TYPE OF HEADS ARE |
| CURRENTLY IN USE. PLEASE REFER TO THE 2010 FBC-B |
| SECTION 709.1 EXCEPTION #3 THAT WILL GREATLY EFFECT |
| YOUR DESIGN AND CODE COMPLIANCE. EXCEPTION 3. IN |
| MINI-WAREHOUSES/SELF-STORAGE BUILDINGS, WALLS USED TO |
| SEPARATE TENANTS SHALL NOT BE REQUIRED TO HAVE |
| FIRE-RESISTANCE RATING, PROVIDED A SPRINKLER SYSTEM |
| MEETING THE REQUIREMENTS OF ORDINARY HAZARD GROUP II AS |
| DEFINED BY NFPA 13, IS INSTALLED EMPLOYING QUICK |
| RESPONSE HEADS. |
| |
| 2) LIFE SAFETY SHEET 1.1 & 1.2 IT APPEARS THAT |
| STAIRWELL 1 ON THE 1ST FLOOR & 2ND FLOOR HAS BEEN |
| CLOSED UP AND NOW A VOID SPACE? THAT WILL LEAVE (3) |
| UNENCLOSED EXITS. THIS MAY STILL BE A STORAGE OCCUPANCY |
| 2010 FLORIDA EXISITNG BUILDING CODE 705.3 NUMBER OF |
| EXITS. THE NUMBER OF EXITS SHALL BE IN ACCORDANCE WITH |
| THE APPROPRIATE SECTIONS OF THE FLORIDA FIRE PREVENTION |
| CODE. |
| NFPA 1 -14.6.1.3 IN EXISTING BUILDINGS, WHERE A 2 STORY |
| EXIT ENCLOSURE CONNECTS THE STORY OF EXIT DISCHARGE |
| WITH AN ADJACENT STORY, THE EXIT SHALL BE PERMITTED TO |
| BE ENCLOSED ONLY ON THE STORY OF EXIT DISCHARGE, |
| PROVIDED THAT NOT LESS THAN 50 % OF THE NUMBER AND |
| CAPACITY OF EXITS ON THE STORY OF EXIT DISCHARGE ARE |
| INDEPENDENT OF SUCH ENCLOSURES. THE SAME LANGUAGE IS |
| FOUND UNDER NFPA 101. 7.2.2.5.1.3. |
| NEITHER STAIR # 107 OR 111 HAVE A ENCLOSURE AT THE |
| BOTTOM OF THE STAIRWELL THAT LEAD TO THE EXTERIOR OF |
| THE BUILDING. |
| |
| 3) LS1.1 PLEASE PROVIDE A COST BREAK DOWN WHERE 20% OR |
| $70.00 DOLLARS IN ACCESSIBLE UPGRADES TO THE BUILDING. |
| 2010 FL ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES |
| IN THE EVENT OF DISPROPORTIONALITY. |
| WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH |
| OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS |
| DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION, |
| THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE |
| EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING |
| DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE |
| ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE |
| ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE |
| FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN |
| ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST |
| ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| ALARMS. |
| |
| 4A) THE PLANS INDICATE A NEW ELEVATOR, THIS ELEVATOR |
| WILL NEED TO COMPLY WITH THE 2010 FBC-ACCESSIBILITY |
| CODE 3001.3 ACCESSIBILITY. |
| PASSENGER ELEVATORS ARE REQUIRED TO BE ACCESSIBLE BY |
| THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| |
| 4B) NEW WORK. 2010 FBC-B 3001.5.1 EACH NEW ELEVATOR |
| SHALL COMPLY WITH THE FLORIDA ELEVATOR SAFETY CODE THAT |
| WAS IN EFFECT AT THE TIME OF RECEIPT OF APPLICATION FOR |
| THE CONSTRUCTION PERMIT FOR THE ELEVATOR. |
| |
| 5) THE LIFE SAFETY SHEETS NOR ARCHITECTURAL SHEETS SHOW |
| THE ELEVATOR SHAFT AS 1 HOUR FIRE RATEDOR FOR THE |
| MACHANICAL ROOM. 2010 FBC-B |
| 3002.1 HOISTWAY ENCLOSURE PROTECTION. |
| ELEVATOR, DUMBWAITER AND OTHER HOISTWAY ENCLOSURES |
| SHALL BE SHAFT ENCLOSURES COMPLYING WITH SECTION 708. |
| 3002.1.1 OPENING PROTECTIVES. |
| OPENINGS IN HOISTWAY ENCLOSURES SHALL BE PROTECTED AS |
| REQUIRED IN CHAPTER 7. |
| |
| 6) LIFE SAFETY & A1.1 SHOW A WALL TYPE # 5 WITH FOAM |
| SHEET INSULATION. SHEET A3.2 DETAIL # 5 INDICATES THE |
| FOAM INSULATION WALL PANELS TO BE 5 " IN THICKNESS |
| INFILL BETWEEN THE DOUBLE T 2ND FLOOR PRECAST BEAM AND |
| FLOORING SYSTEM. PLEASE PROVIDE THE MANUFACTURERS |
| SPECIFICATION FOR THE FOAM INSULATION AND COMPLIANCE |
| WITH FBC-B 2603.3 AND OR EXCEPTIONS. ALSO SEE 2010 |
| FBC-MECHANICAL FOR USE IN PLENUMS FBC-M 602.2 & |
| 602.2.1. |
| |
| 7) SHEET S-1 PROVIDES THE WIND DESIGN FOR THE NEW |
| EXTERIOR DOOR ELEMENTS BUT NO PRODUCT APPROVALS WERE |
| SUBMITTED WITH THIS REVIEW. |
| 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 |
| COMPONENTS & CLADDING |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (B) WINDOWS |
| (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| LOUVERS, |
| |
| 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 9) THE SHEET LS 1.1 LIST THIS BUILDING AS A TYPE VA |
| BUILDING PLEASE PROVIDE HOW THE 1 HR FIRE RATING WILL |
| BE ACHIEVED AND CODE COMPLIANCE WITH FBC-B TABLE 601. |
| THE PLANS SHOW NEW STRUCTURAL MEMBERS WITH THE NEW HOLE |
| BEING CUT INTO THE FLOOR. |
| |
| 10) SINCE THIS BUILDING IS CHANGING THE USAGE TYPE FROM |
| STORAGE TO MINI STORAGE UNITS TTHE PLANS WILL NEED TO |
| GO TO P B C IMPACT FEE OFFICE FOR ASSESSMENT OF IMPACT |
| FEES. |
| |