2014-06-23 07:48:15BUILDING PLAN REVIEW
 PERMIT: 14050913
 ADD: 1016 CLARE SUITE # 3
 CONT: RIELLY CONSTRUCTION
 TEL: (561)262-6876
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY JUNE 23/ 2014
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET LS 1.1 DESIGN STANDAARDS &
 CODE REQUIREMENT HEADING LIST THE BUILDING AS FULLY
 SPRINKLERED WITH A NFPA 13 SYSTEM. PLEASE NOTE THAT THE
 SPRINKLERS DOES NOT STATE WHAT TYPE OF HEADS ARE
 CURRENTLY IN USE. PLEASE REFER TO THE 2010 FBC-B
 SECTION 709.1 EXCEPTION #3 THAT WILL GREATLY EFFECT
 YOUR DESIGN AND CODE COMPLIANCE. EXCEPTION 3. IN
 MINI-WAREHOUSES/SELF-STORAGE BUILDINGS, WALLS USED TO
 SEPARATE TENANTS SHALL NOT BE REQUIRED TO HAVE
 FIRE-RESISTANCE RATING, PROVIDED A SPRINKLER SYSTEM
 MEETING THE REQUIREMENTS OF ORDINARY HAZARD GROUP II AS
 DEFINED BY NFPA 13, IS INSTALLED EMPLOYING QUICK
 RESPONSE HEADS.
  
 2) LIFE SAFETY SHEET 1.1 & 1.2 IT APPEARS THAT
 STAIRWELL 1 ON THE 1ST FLOOR & 2ND FLOOR HAS BEEN
 CLOSED UP AND NOW A VOID SPACE? THAT WILL LEAVE (3)
 UNENCLOSED EXITS. THIS MAY STILL BE A STORAGE OCCUPANCY
 2010 FLORIDA EXISITNG BUILDING CODE 705.3 NUMBER OF
 EXITS. THE NUMBER OF EXITS SHALL BE IN ACCORDANCE WITH
 THE APPROPRIATE SECTIONS OF THE FLORIDA FIRE PREVENTION
 CODE.
 NFPA 1 -14.6.1.3 IN EXISTING BUILDINGS, WHERE A 2 STORY
 EXIT ENCLOSURE CONNECTS THE STORY OF EXIT DISCHARGE
 WITH AN ADJACENT STORY, THE EXIT SHALL BE PERMITTED TO
 BE ENCLOSED ONLY ON THE STORY OF EXIT DISCHARGE,
 PROVIDED THAT NOT LESS THAN 50 % OF THE NUMBER AND
 CAPACITY OF EXITS ON THE STORY OF EXIT DISCHARGE ARE
 INDEPENDENT OF SUCH ENCLOSURES. THE SAME LANGUAGE IS
 FOUND UNDER NFPA 101. 7.2.2.5.1.3.
 NEITHER STAIR # 107 OR 111 HAVE A ENCLOSURE AT THE
 BOTTOM OF THE STAIRWELL THAT LEAD TO THE EXTERIOR OF
 THE BUILDING.
  
 3) LS1.1 PLEASE PROVIDE A COST BREAK DOWN WHERE 20% OR
 $70.00 DOLLARS IN ACCESSIBLE UPGRADES TO THE BUILDING.
 2010 FL ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 4A) THE PLANS INDICATE A NEW ELEVATOR, THIS ELEVATOR
 WILL NEED TO COMPLY WITH THE 2010 FBC-ACCESSIBILITY
 CODE 3001.3 ACCESSIBILITY.
 PASSENGER ELEVATORS ARE REQUIRED TO BE ACCESSIBLE BY
 THE FLORIDA BUILDING CODE, ACCESSIBILITY.
  
 4B) NEW WORK. 2010 FBC-B 3001.5.1 EACH NEW ELEVATOR
 SHALL COMPLY WITH THE FLORIDA ELEVATOR SAFETY CODE THAT
 WAS IN EFFECT AT THE TIME OF RECEIPT OF APPLICATION FOR
 THE CONSTRUCTION PERMIT FOR THE ELEVATOR.
  
 5) THE LIFE SAFETY SHEETS NOR ARCHITECTURAL SHEETS SHOW
 THE ELEVATOR SHAFT AS 1 HOUR FIRE RATEDOR FOR THE
 MACHANICAL ROOM. 2010 FBC-B
 3002.1 HOISTWAY ENCLOSURE PROTECTION.
 ELEVATOR, DUMBWAITER AND OTHER HOISTWAY ENCLOSURES
 SHALL BE SHAFT ENCLOSURES COMPLYING WITH SECTION 708.
 3002.1.1 OPENING PROTECTIVES.
 OPENINGS IN HOISTWAY ENCLOSURES SHALL BE PROTECTED AS
 REQUIRED IN CHAPTER 7.
  
 6) LIFE SAFETY & A1.1 SHOW A WALL TYPE # 5 WITH FOAM
 SHEET INSULATION. SHEET A3.2 DETAIL # 5 INDICATES THE
 FOAM INSULATION WALL PANELS TO BE 5 " IN THICKNESS
 INFILL BETWEEN THE DOUBLE T 2ND FLOOR PRECAST BEAM AND
 FLOORING SYSTEM. PLEASE PROVIDE THE MANUFACTURERS
 SPECIFICATION FOR THE FOAM INSULATION AND COMPLIANCE
 WITH FBC-B 2603.3 AND OR EXCEPTIONS. ALSO SEE 2010
 FBC-MECHANICAL FOR USE IN PLENUMS FBC-M 602.2 &
 602.2.1.
  
 7) SHEET S-1 PROVIDES THE WIND DESIGN FOR THE NEW
 EXTERIOR DOOR ELEMENTS BUT NO PRODUCT APPROVALS WERE
 SUBMITTED WITH THIS REVIEW.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS,
  
 8) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) THE SHEET LS 1.1 LIST THIS BUILDING AS A TYPE VA
 BUILDING PLEASE PROVIDE HOW THE 1 HR FIRE RATING WILL
 BE ACHIEVED AND CODE COMPLIANCE WITH FBC-B TABLE 601.
 THE PLANS SHOW NEW STRUCTURAL MEMBERS WITH THE NEW HOLE
 BEING CUT INTO THE FLOOR.
  
 10) SINCE THIS BUILDING IS CHANGING THE USAGE TYPE FROM
 STORAGE TO MINI STORAGE UNITS TTHE PLANS WILL NEED TO
 GO TO P B C IMPACT FEE OFFICE FOR ASSESSMENT OF IMPACT
 FEES.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER