2014-09-23 07:45:21 | DATE: 9/23/2014 |
| PROJECT: IMPACT WINDOWS SIGN |
| PERMIT#: 14050899 |
| CODE: 2008 EDITION OF THE NEC |
| 2010 EDITION OF THE FBC |
| 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| |
| 2ND ELECTRICAL PLAN REVIEW |
| ACTION: PROVISO |
| |
| 1) NEC 600.5 |
| EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO PEDESTRIANS |
| SHALL BE PROVIDED WITH AT LEAST ONE OUTLET SUPPLIED BY |
| A BRANCH CIRCUIT RATED AT LEAST 20 AMPERES THAT |
| SUPPLIES NO OTHER LOAD. |
| |
| 2) 600.3 LISTING. |
| ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING ? |
| FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND |
| INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS |
| OTHERWISE APPROVED BY SPECIAL PERMISSION. |
| |
| 3) NEC 600.6(A)(1) LOCATION. |
| DISCONNECTS. EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR |
| FEEDER CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR |
| OUT-LINE LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN |
| EXTERNALLY OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL |
| OPEN ALL UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN |
| OR OUTLINE LIGHTING SYSTEM THAT IT CONTROLS. |
| |
| 4) FBC-E 505.2.4 |
| ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1 SHALL |
| HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT OR WHEN |
| NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR & TIME |
| CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME SWITCHES |
| SHALL BE CAPABLE OF RETAINING PROGRAMING DURING A LOSS |
| OF POWER FOR A MINIMUM OF 10 HOURS. |
| |
| 5) 600.4 MARKINGS. |
| (A) SIGNS AND OUTLINE LIGHTING SYSTEMS. SIGNS AND |
| OUTLINE LIGHTING SYSTEMS SHALL BE MARKED WITH THE |
| MANUFACTURER?S NAME, TRADEMARK, OR OTHER MEANS OF |
| IDENTIFICATION; AND INPUT VOLTAGE AND CURRENT RATING. |
| (B) SIGNS WITH LAMPHOLDERS FOR INCANDESCENT LAMPS. |
| SIGNS AND OUTLINE LIGHTING SYSTEMS WITH LAMPHOLDERS FOR |
| INCANDESCENT LAMPS SHALL BE MARKED TO INDICATE THE |
| MAXIMUM ALLOWABLE LAMP WATTAGE PER LAMPHOLDER. THE |
| MARKINGS SHALL BE PERMANENTLY INSTALLED, IN LETTERS AT |
| LEAST 6 MM (1?4 IN.) HIGH, AND SHALL BE LOCATED WHERE |
| VISIBLE DURING RELAMPING. |
| (C) SECTION SIGNS. SECTION SIGNS SHALL BE MARKED TO |
| INDICATE THAT FIELD-WIRING AND INSTALLATION |
| INSTRUCTIONS ARE REQUIRED. THE ELECTRICAL CONNECTIONS |
| TO SAME ARE UNDER A DIFFERENT PERMIT. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |