2014-07-01 15:35:45DATE: 7/1/2014
 PROJECT: MALONEY RESIDENCE
 PERMIT#: 14050884
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 ELECTRICAL PERMIT APPLICATION REQUIRED FROM QUALIFIED,
 REGISTERED ELECTRICAL CONTRACTOR. PLANS TO BE REVISED
 TO CORRECT THE FOLLOWING DEFICIENCIES:
  
 1) ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT
 DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. FBC-R 107.3.5.3
  
 2) A GROUNDING ELECTRODE SYSTEM IS REQUIRED AT THE
 SERVICE. NEC 250.50
  
 3) AN INTER SYSTEM BOND IS REQUIRED AT THE SERVICE. NEC
 250.94
  
 4) ALL NEW GENERAL PURPOSE OUTLETS MUST BE AFCI
 PROTECTED. NEC 210.12
  
 5) NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11
  
 6) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE
 BATHROOMS. NEC 210.11 (C)(3)
  
 7) KITCHEN COUNTER TOP RECEPTACLES SHALL BE SUPPLIED BY
 NO FEWER THAN TWO SMALL APPLIANCE BRANCH CIRCUITS. NEC
 210.52(B)(3)
  
 8) AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT
 EACH ISLAND COUNTERTOP SPACE WITH A LONG DIMENSION OF
 24" OR GREATER AND A SHORT DIMENSION OF 12" OR GREATER.
 NEC 210.52(C)(2)
  
 SEPARATE PERMITS REQUIRED FOR GENERATOR, SWIMMING POOL,
 STRUCTURED CABLING FOR NETWORK, SECURITY, AUDIO/VIDEO,
 CCTV
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.
 561-805-6717 OR [email protected]
  
  