Plan Review Notes
Plan Review Notes For Permit 14050884
Permit Number 14050884
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-27 16:40:372010 FBC
  
 DENIED BY BUILDING
  
 1) THE ARCHITECT IS REQUIRED TO SIGN AND SEAL THE PLANS
 THAT ARE SUBMITTED FOR PUBLIC RECORD. FAC 61G1-16.003
  
 2) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C.
 PLEASE REVISE PLANS AND ADJUST THE WINDLOAD PRESSURES.
 FBCR 301.2.1.4.3
  
 3) SUBMIT TWO SETS OF A DRAINAGE PLAN THAT SHOWS
 COMPLIES WITH FBCR 401.3 SURFACE DRAINAGE SHALL BE
 DIVERTED TO A STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION THAT DOES NOT CREATE A HAZARD. IT
 CAN NOT BE DRAINED ONTO ADJACENT LOTS.
  
 4) SHOW THAT THE DOOR FROM THE GARAGE TO THE KITCHEN
 COMPLIES WITH FBCR 302.5.1.
  
 5) SHOW COMPLIANCE WITH FBCR 302.6 FOR DWELLING /
 GARAGE FIRE SEPARATION.
  
 6) SHOW COMPLIANCE WITH FBCR 806 FOR ROOF VENTILATION.
  
 7) SHOW COMPLIANCE WITH FBCR 807.1 FOR ATTIC ACCESS.
  
 8) PROVIDE A WALL SECTION THAT SHOWS THE WALL AND ATTIC
 INSULATION ( UN-VENTED ATTIC ), ETC. CITY AMENDMENTS
 107.2.1
  
 9) SPECIFY THE LENGTH OF THE OVERHANG AND THE SOFFIT
 MATERIAL THAT WILL BE INSTALLED. CITY AMENDMENTS
 107.2.1 AND FBCR 616.1
  
 10) SPECIFY THE MATERIAL THAT WILL BE INSTALLED ON THE
 CEILING OF THE LOGGIA. CITY AMENDMENTS 107.2.1
  
 11) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS, LISTING AND INSTALLATION INSTRUCTIONS
 FOR THE BUILT-IN BBQ ON THE LOGGIA. FBCR M1901.2 AND
 G2408.1.
  
 12) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION REPORT
 FOR THE SPRAY FOAM INSULATION IF IT IS USED. FBCR 316
  
 13) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.3.4.1
  
 14) THE PRODUCT APPROVAL FOR THE WOOD FIXED WINDOWS NOA
 NO. 11-1024.07 HAS BEEN SUPERSEDED BY NOA NO.
 14-0402.02. PLEASE SUBMIT THE CURRENT NOA. DCA RULE
 9N-3
  
 15) THE DRAWINGS THAT WERE SUBMITTED FOR THE FIBERGLASS
 SWING DOOR AT THE GARAGE WERE NOT SHRUNK TO FIT ON AN
 8" X 11" PAGE AND SOME OF THE INFORMATION WAS CUT OFF.
 PLEASE PROVIDE NEW PAGES WITH COMPLETE INFORMATION. DCA
 RULE 9N-3 AND CITY AMENDMENTS 107.2.1
  
 16) PLEASE PROVIDE A RESPONSE LETTER THAT INDICATES HOW
 EACH OF THE REVIEW ITEMS WAS ADDRESSED. THIS WILL HELP
 TO REDUCE PLAN REVIEW TIME.
  