Plan Review Notes
Plan Review Notes For Permit 14050851
Permit Number 14050851
Review Stop P
Sequence Number 1
Notes
Date Text
2014-05-25 10:15:21PLUMBING PLAN REVIEW
 PERMIT: 14050851
 ADD: 777 S FLAGLER DR. SUITE # 900 W
 CONT: FISHER
 TEL: (561)691-4716
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUNDAY MAY 25 TH/ 2014
 ACTION: DENIED
  
 1A) SHEET P1.1 NOTE # 3 SHOWS THE USE OF AN AIR
 ADMITTANCE VALVE, PLEASE PROVIDE HOW MANY FLOORS ARE
 LOCATED ABOVE THIS SUITE AND SHOW COMPLIANCE WITH 2010
 FBC-PLUMBING 917.3.1 LOCATION OF BRANCH. THE HORIZONTAL
 BRANCH DRAIN SHALL CONNECT TO THE DRAINAGE STACK OR
 BUILDING DRAIN A MAXIMUM OF FOUR BRANCH INTERVALS FROM
 THE TOP OF THE STACK.
  
 1B) PLEASE ALSO CONSIDER RETURN AIR PLENUMS AS FOUND ON
 SHEETS M2.1, PLEASE REVIEW 2010 FBC-PLUMBING SECTION
 17.8 PROHIBITED INSTALLATIONS. AIR ADMITTANCE VALVES
 SHALL NOT BE LOCATED IN SPACES UTILIZED AS SUPPLY OR
 RETURN AIR PLENUMS.
  
 2) SHEET P1.1 NOTE # 11 INDICATES THE USE OF A NEW
 DRINKING FOUNTAIN BUT THE SHEET DOES NOT SHOW A WASTE
 TO THE SANITARY SEWER. THE 2010 FBC-PLUMBING TABLE
 709.1 DRINKING FOUNTAINS 1/2 DFU'S AND MINIMUM TRAP
 SIZE OF 1 1/4 INCH.
  
 3) 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING. DRINKING
 FONTAINS UNDER THE FL ACCESSIBILITY CODE ARE REQUIRED
 TO COMPLY WITH 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
 NO MONIES HAVE BEEN SPENT UNDER THE DIPROPORTIONATE
 COST 202.4.1.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]