2014-05-25 09:47:25 | BUILDING PLAN REVIEW |
| PERMIT: 14050851 |
| ADD: 777 S FLAGLER DR. SUITE # 900 W |
| CONT: FISHER |
| TEL: (561)691-4716 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SUNDAY MAY 25 TH/ 2014 |
| ACTION: DENIED |
| |
| NOTE, NO ACTION IS REQUIRED, ROOMS 904 & 912 FALL UNDER |
| THE COMMON PATH OF TRAVEL BUSINESS OCC. SPRINKLERED |
| BLDG 100 FEET WITH A OCCUPANT LOAD OF LESS THAN 49 |
| OCCUPANTS. |
| |
| 1) THIS PERMIT IS A PHASED PERMIT, WITH A PHASE I AND |
| PHASE II. THE PLANS DO NOT INDICATE IF THE PHASE II |
| PART OF THE PROJECT WILL STATE AFTER PHASE 1 IS |
| COMPLETE OR WILL THEY |
| STAT AT THE SAME TIME AND ONLY PHASE 1 LOOK FOR A |
| TEMPORARY C.O.? THE CONCERN IS THE 2ND PHASE |
| COMPLETEING BEOFE THE 1ST PHASE, AND IF SO THE 2ND |
| REQUIRED EXIT THAT WOULD BE IN THE PHASE 1 PORTION OF |
| THE PERMIT. OCCUPANT LOADS > THAN 49 OCCUPANTS |
| REQUIRING THE 2 EXITS, 2010 FBC-B 1015.1. |
| |
| 2) THIS TENANT SPACE HAS 5 AREAS OF CONFERENCE ROOMS |
| PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 508.2.1 THAT |
| THESE AREAS CAN BE CONSIDERED ACCESSORY OCCUPANCIES |
| UNDER 2010 FBC-B 508.2.1. THE AREA FOR ALL BREAK ROOMS |
| & CONFERENCE ROOMS HAS TO BE TAKEN INTO ACCOUNT. |
| 508.2.1 AREA LIMITATIONS. AGGREGATE ACCESSORY |
| OCCUPANCIES SHALL NOT OCCUPY MORE THAN 10 PERCENT OF |
| THE BUILDING AREA OF THE STORY IN WHICH THEY ARE |
| LOCATED AND SHALL NOT EXCEED THE TABULAR VALUES IN |
| TABLE 503, WITHOUT BUILDING AREA INCREASES IN |
| ACCORDANCE WITH SECTION 506 FOR SUCH ACCESSORY |
| OCCUPANCIES. |
| |
| BOAF INFORMAL INTERPRETATION REPORT # 6506 |
| DATE: THU JUN 3 2010 |
| REPORT: 6506 |
| CODE: BUILDING CODE YEAR: 2007 |
| SECTION: 508.3.1 |
| QUESTION: |
| IS IT THE INTENT OF FLORIDA BUILDING CODE - BUILDING |
| SECTION 508.3.1, EXCEPTION 1, TO NOT REQUIRE FIRE |
| SEPARATION BETWEEN THE |
| PRIMARY OCCUPANCY AND MULTIPLE ACCESSORY OCCUPANCIES, |
| WHEN EACH ACCESSORY OCCUPANCY IS LESS THAN 750 SQ. FEET |
| EACH OR |
| ONLY WHEN THE TOTAL OF ALL ACCESSORY OCCUPANCIES IS |
| LESS THAN 750 SQ. FEET IN AREA? |
| COMMENT: |
| AN EXAMPLE WOULD BE A BUSINESS OCCUPANCY WITH ONE |
| ACCESSORY AREA OF 700SF FOR GATHERINGS AND MEETINGS AND |
| A SECOND |
| ACCESSORY AREA OF 650SF FOR FITNESS AND WORKOUT. IS THE |
| EXCEPTION LIMITATION OF 750 S.F. MAX APPLIED TO EACH |
| ACCESSORY AREA, IN |
| WHICH CASE THIS BUILDING WOULD COMPLY, OR TO THE |
| COMBINED TOTAL OF THE TWO ACCESSORY AREAS, IN WHICH |
| CASE IT WOULD NOT? |
| ANSWER: |
| NO. CONSIDERING BOTH SPACES TO BE ASSEMBLY USES LOCATED |
| ON THE SAME FLOOR, THE EXCEPTION TO FLORIDA BUILDING |
| CODE - BUILDING |
| SECTION 508.3.1 WOULD NOT REQUIRE SEPARATION OF EITHER |
| SPACE. HOWEVER, THE SECTION TO WHICH THE EXCEPTION |
| RELATES WOULD LIMIT |
| THE AGGREGATE ACCESSORY OCCUPANCIES TO 10% OF THE AREA |
| OF THE FLOOR ON WHICH THEY ARE LOCATED. IF THE AREA OF |
| TWO COMBINED |
| ASSEMBLY USES EXCEEDED 10%, THEN AT LEAST ONE OF THE |
| ASSEMBLY USES WOULD REQUIRE FIRE RESISTANT RATED |
| SEPARATION OF 2 HOURS IN |
| A NON-SPRINKLED BUILDING AND 1 HOUR IN A BUILDING |
| SPRINKLED THROUGHOUT. |
| COMMENTARY: |
| NONE. |
| NOTICE: THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA, |
| IN COOPERATION WITH THE FLORIDA BUILDING COMMISSION, |
| THE FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ICC, |
| AND INDUSTRY AND PROFESSIONAL EXPERTS OFFER THIS |
| INTERPRETATION OF THE FLORIDA BUILDING CODE IN THE |
| INTEREST OF CONSISTENCY IN THEIR APPLICATION STATEWIDE. |
| THIS INTERPRETATION IS INFORMAL, NON-BINDING AND |
| SUBJECT TO ACCEPTANCE AND APPROVAL BY THE LOCAL |
| BUILDING OFFICIAL. |
| |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |