Plan Review Notes For Permit 14050847 |
Permit Number |
14050847 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-06-11 18:39:50 | THE FOLLOWING PROVISOS HAVE BEEN MADE A CONDITION OF | | APPROVAL FOR PERMIT 14050847: | | | | 1. ARC-FAULT PROTECTION SHALL COMPLY W/NEC 210.12(B) | | 2. SMOKE DET. PLACEMENT SHALL COMPLY W/FBC-R 314 & 315 | | 3. FEEDER #1 SHALL HAVE A 1/0 CU GEC PER NEC 250.66 | | 4. INTER-SYSTEM BONDING TERMINAL REQ?D AS PER NEC | | 250.94 | | 5. ALL METAL PIPING SYSTEMS (GAS, COLD WATER, | | STRUCTURAL STEEL ETC. SHALL BE BONDED SHALL BE BONDED | | AS IN NEC 250.104 | | 6. ALL EXTERIOR RECEPTACLES SHALL BE LISTED ?WR? AS IN | | 406.8 | | 7. TAMPER-RESISTANT RECEPTACLES ARE REQ?D AS PER NEC | | 406.11 | | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL | | PLANS EXAMINER | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | FOLLOWING LINK: | | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | US.ASPX | | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | ABOVE THE SECOND PERMIT INFORMATION). | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR | | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER | | PERMIT CONDITIONS. | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | I CAN BE REACHED AT 561-805-6718 OR [email protected] | | |
|