Plan Review Notes For Permit 14050789 |
Permit Number |
14050789 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-06-02 12:08:05 | 5501 CORPORATE WAY | | | | 1ST ELECTRICAL REVIEW. | | | | ACTION: DENIED. | | | | CODE REFFERENCE: 2008 EDITION OF THE NEC, 2010 EDITION | | OF THE FLORIDA BUILDING CODE. | | | | COMMENTS: | | | | 1) DISCONNECT REQUIRED. NEC 600.6 | | | | 2) ADDITIONAL DETAILS REQUIRED ON HOW CIRCUITRY ENTERS | | THE SIGN. FBC 107.2.1 | | | | 3) ADDITIONAL DETAIL REQUIRED ON LOW VOLTAGE FOR THE | | SPEAKER WIRING. FBC 107.2.1 | | | | 4) PROVIDE DETAILS ON THE LOW VOLTAGE DATA AND SPEAKER | | CABLING FBC 107.2.1 | | | | 5) LOW VOLTAGE CABLES INSTALLED IN A WET LOCATION SHALL | | BE RATED FOR THE ENVIRONMENT IN WHICH THEY ARE | | INSTALLED. NEC 110.3 | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR AT [email protected] | | | | |
|