Plan Review Notes
Plan Review Notes For Permit 14050778
Permit Number 14050778
Review Stop E
Sequence Number 1
Notes
Date Text
2014-06-11 08:37:29DATE: 6/11/2014
 PROJECT: LINCOLN TOWER CONDO, COOLING TOWER.
 PERMIT#: 14050778
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 ELECTRICAL PLAN REVIEW
  
 1ST REVIEW
 ACTION: DENIED
  
 1) CLARIFY SCOPE OF ELECTRICAL WORK. NOTES DISCUSS THE
 DEMOLITION OF LIGHTING, CONDUIT AND WIRE. PLEASE
 INDICATE ON FLOOR PLAN THE SPECIFIC ITEMS TO BE REMOVED
 AND OR REPLACED. INDICATE SPECIFICALLY WHAT IS EXISTING
 TO REMAIN AND WHAT IS PROPOSED TO BE NEW. INDICATE
 MEATHODS AND MATERIALS TO BE USED IN THE COMPLETION OF
 THE PROJECT. FBC 107.2.1
  
 2) MINIMUM PLAN REVIEW CRITERIA. ELECTRICAL: WIRING
 SERVICES FEEDERS AND BRANCH CIRCUITS OVERCURRENT
 PROTECTION GROUNDING WIRING METHODS AND MATERIALS GFCIS
 EQUIPMENT SPECIAL OCCUPANCIES, EMERGENCY SYSTEMS,
 COMMUNICATION SYSTEMS, LOW VOLTAGE, LOAD CALCULATIONS,
 DESIGN FLOOD ELEVATION. FBC 107.3.5.1.2 ELECTRICAL
  
 3) THE BRANCH CIRCUIT FEEDING BATTERY BACKED EMERGENCY
 AND EXIT LIGHTS SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES. NEC 701.11(G)
  
 4) ILLUMINATION OF MEANS OF EGRESS SHALL BE PROVIDED IN
 ACCORDANCE WITH THIS SECTION FOR EVERY BUILDING AND
 STRUCTURE. FOR THE PURPOSE OF THIS REQUIRMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCELATORS, WALKWAYS AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY. ADDITIONAL
 EMERGENCY BATTERY BACKED LIGHTING IS REQUIRED FOR
 ADAQUATE ILLUMINATION OF THE EGRESS PATH. FBC 1006.1.1
  
 5) INDICATE DISCONNECTS WHERE REQUIRED AT A/C EQUIPMENT
 ETC.. NEC 440.14
  
 6) GFCI OUTLET REQUIRED AT A/C EQUIPMENT. NEC 210.63
  
 7) THE CALCULATED LOAD OF A FEEDER OR SERVICE SHALL NOT
 BE LESS THAN THE SUM OF THE LOADS ON THE BRANCH
 CIRCUITS SUPPLIED AS DETERMINED BY PART II OF ARTICLE
 220, AFTER ANY APPLICABLE DEMAND FACTORS PERMITTED BY
 PART III OR IV OR REQUIRED BY PART V HAVE BEEN APPLIED.
 PROVIDE A CALCULATED LOAD SUMMARY TO VERIFY THE
 EXISTING FEEDER IS ADAQUATE TO SERVE THE NEW LOADS. NEC
 220.40
  
 8) INDICATE COMPLIANCE WITH ARITCAL 110.26 IN THE NEC
 WHICH REQUIRES THAT SUFFICIENT ACCESS AND WORKING SPACE
 SHALL BE PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL
 EQUIPMENT TO PERMIT READY AND SAFE OPERATION AND
 MAINTENANCE OF SUCH EQUIPMENT. NEC 110.26
  
 9) PROVIDE SAFETY LABELING FOR FLASH PROTECTION AND FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.22, 110.16, 110.22
  
 10) MECHANICAL EQUIPMENT, ELECTRICAL, TRANSFORMER,
 TELEPHONE EQUIPMENT, ELEVATOR MACHINE OR SIMILAR ROOMS,
 A LISTED SMOKE DETECTOR SHALL BE INSTALLED.
 FBC-907.2.18.1 LISTED SINGLE AND MULTIPLE STATION SMOKE
 ALARMS COMPLYING WITH UL 217 SHALL BE INSTALLED IN
 ACCORDANCE WITH SECTIONS 907.2.11.1 THROUGH 907.2.11.4
 AND NFPA 72
  
 11) ALL COMPONENTS AND CABLES SHALL BE UL LISTED AND
 LABELED FOR USE IN THE MANNER INSTALLED. NEC 110.3
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.