Date |
Text |
2014-06-13 17:50:13 | BUILDING PLAN REVIEW |
| PERMIT: 14050759 |
| ADD: 8100 IBIS BLVD |
| CONT:THE WEITZ CO. |
| TEL: (561)686-5511 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: FRIDAY JUNE 13/ 2014 |
| ACTION: DENIED |
| |
| 1) SHEET AS 103 THE ENLARGED DEMO SITE PLAN. IT APPEARS |
| THE GOLF PRO-SHOP 1ST FLOOR WILL BE OCCIPIED AND OPEN |
| FOR THE PUBLIC. IF SO PLEASE PROVIDE WHAT SAFE GAURDS |
| WILL BE PUT IN PLACE TO INSURE THIER SAFETY ENTERING |
| AND EXITING THE BUILDING WHILE THE REMAINDER OF THE |
| SITE IS UNDER CONSTRUCTION. |
| 2010 FBC-B 3302.1 REMODELING AND ADDITIONS. REQUIRED |
| EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE PROTECTION |
| DEVICES AND SANITARY SAFEGUARDS SHALL BE MAINTAINED AT |
| ALL TIMES DURING REMODELING, ALTERATIONS, REPAIRS OR |
| ADDITIONS TO ANY BUILDING OR STRUCTURE. |
| 3302.2 MANNER OF REMOVAL. WASTE MATERIALS SHALL BE |
| REMOVED IN A MANNER WHICH PREVENTS INJURY OR DAMAGE TO |
| PERSONS, ADJOINING PROPERTIES. |
| 3303.2 PEDESTRIAN PROTECTION. THE WORK OF DEMOLISHING |
| ANY BUILDING SHALL NOT BE COMMENCED UNTIL PEDESTRIAN |
| PROTECTION IS IN PLACE AS REQUIRED BY THIS CHAPTER. |
| |
| 2) THIS SAME SHEET IT APPEARS NO REMODELING WILL TAKE |
| PLACE ON THE INTERIOR OF THE GOLF PRO-SHOP AND WILL BE |
| OPEN TO THE PUBLIC, PLEASE PROVIDE A RATED FIRE BARRIER |
| BETWEEN THE ACTIVE WORK SITE 1ST FLOOR OF THE CLUBHOUSE |
| AND PRO SHOP. 3306.5 BARRIERS. BARRIERS SHALL BE A |
| MINIMUM OF 8 FEET (2438 MM) IN HEIGHT AND SHALL BE |
| PLACED ON THE SIDE OF THE WALKWAY NEAREST THE |
| CONSTRUCTION. BARRIERS SHALL EXTEND THE ENTIRE LENGTH |
| OF THE CONSTRUCTION SITE. OPENINGS IN SUCH BARRIERS |
| SHALL BE PROTECTED BY DOORS WHICH ARE NORMALLY KEPT |
| CLOSED. |
| |
| 3) F] 3309.1 WHERE REQUIRED. |
| ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR |
| DEMOLITION SHALL BE PROVIDED WITH NOT LESS THAN ONE |
| APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH |
| SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD |
| AS FOLLOWS: |
| |
| 3.1.AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| COMBUSTIBLE MATERIALS HAVE ACCUMULATED. |
| |
| 3.2.IN EVERY STORAGE AND CONSTRUCTION SHED. |
| |
| 3.3.ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| |
| 4) 3309.2 FIRE HAZARDS. THE PROVISIONS OF THIS CODE AND |
| THE FLORIDA FIRE PREVENTION CODE SHALL BE STRICTLY |
| OBSERVED TO SAFEGUARD AGAINST ALL FIRE HAZARDS |
| ATTENDANT UPON CONSTRUCTION OPERATIONS. |
| |
| 5) DURING THE DEMOLITION AS WELL AS THE FONDATION WORK |
| A THRESHOLD INSPECTOR SHALL BE ON SITE. THRESHOLD |
| INSPECTION PLAN FL S. S. 553.71(7) " THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| (3) STORIES OR 50 FT IN HEIGHT, OR WHICH HAS AN |
| ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| |
| 6) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| |
| 7) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| REQUIRED BY THIS CODE. A THRESHOLD AGREEMENT MUST BE |
| SIGNED BY THE THRESHOLD INSPECTOR, CONTRACTOR, OWNERS, |
| PLEASE CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| |
| 8) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B. AMENDMENT |
| 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH ARE |
| REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR |
| ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE |
| PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE. |
| |
| 9) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| INSPECTIONS. |
| |
| 9.1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| CONRAD: [email protected] |
| |
| 9.2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| MEETING THE ABOVE CRITERIA. |
| CONTACT KEN CONRAD |
| TEL: 561-805-6666 |
| E-MAIL: [email protected] |
| |
| 10) SHEET S.001 STRUCTURAL NOTES 2310 INDICATE A SOILS |
| REPORT WAS COMPLETED, FOUNDATION SOILS REPORT HD 135558 |
| BY DUNKLEBURGER ENGINEERING & TESTING PLEASE PROVIDE |
| SOILS REPORT AS REQUIRED BY SECTION 2010 FBC-B 1803.5.2 |
| QUESTIONABLE SOIL. |
| WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY |
| OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE |
| SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE |
| BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| |
| 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |