Plan Review Notes
Plan Review Notes For Permit 14050759
Permit Number 14050759
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-13 17:50:13BUILDING PLAN REVIEW
 PERMIT: 14050759
 ADD: 8100 IBIS BLVD
 CONT:THE WEITZ CO.
 TEL: (561)686-5511
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY JUNE 13/ 2014
 ACTION: DENIED
  
 1) SHEET AS 103 THE ENLARGED DEMO SITE PLAN. IT APPEARS
 THE GOLF PRO-SHOP 1ST FLOOR WILL BE OCCIPIED AND OPEN
 FOR THE PUBLIC. IF SO PLEASE PROVIDE WHAT SAFE GAURDS
 WILL BE PUT IN PLACE TO INSURE THIER SAFETY ENTERING
 AND EXITING THE BUILDING WHILE THE REMAINDER OF THE
 SITE IS UNDER CONSTRUCTION.
 2010 FBC-B 3302.1 REMODELING AND ADDITIONS. REQUIRED
 EXITS, EXISTING STRUCTURAL ELEMENTS, FIRE PROTECTION
 DEVICES AND SANITARY SAFEGUARDS SHALL BE MAINTAINED AT
 ALL TIMES DURING REMODELING, ALTERATIONS, REPAIRS OR
 ADDITIONS TO ANY BUILDING OR STRUCTURE.
 3302.2 MANNER OF REMOVAL. WASTE MATERIALS SHALL BE
 REMOVED IN A MANNER WHICH PREVENTS INJURY OR DAMAGE TO
 PERSONS, ADJOINING PROPERTIES.
 3303.2 PEDESTRIAN PROTECTION. THE WORK OF DEMOLISHING
 ANY BUILDING SHALL NOT BE COMMENCED UNTIL PEDESTRIAN
 PROTECTION IS IN PLACE AS REQUIRED BY THIS CHAPTER.
  
 2) THIS SAME SHEET IT APPEARS NO REMODELING WILL TAKE
 PLACE ON THE INTERIOR OF THE GOLF PRO-SHOP AND WILL BE
 OPEN TO THE PUBLIC, PLEASE PROVIDE A RATED FIRE BARRIER
 BETWEEN THE ACTIVE WORK SITE 1ST FLOOR OF THE CLUBHOUSE
 AND PRO SHOP. 3306.5 BARRIERS. BARRIERS SHALL BE A
 MINIMUM OF 8 FEET (2438 MM) IN HEIGHT AND SHALL BE
 PLACED ON THE SIDE OF THE WALKWAY NEAREST THE
 CONSTRUCTION. BARRIERS SHALL EXTEND THE ENTIRE LENGTH
 OF THE CONSTRUCTION SITE. OPENINGS IN SUCH BARRIERS
 SHALL BE PROTECTED BY DOORS WHICH ARE NORMALLY KEPT
 CLOSED.
  
 3) F] 3309.1 WHERE REQUIRED.
 ALL STRUCTURES UNDER CONSTRUCTION, ALTERATION OR
 DEMOLITION SHALL BE PROVIDED WITH NOT LESS THAN ONE
 APPROVED PORTABLE FIRE EXTINGUISHER IN ACCORDANCE WITH
 SECTION 906 AND SIZED FOR NOT LESS THAN ORDINARY HAZARD
 AS FOLLOWS:
  
 3.1.AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE
 COMBUSTIBLE MATERIALS HAVE ACCUMULATED.
  
 3.2.IN EVERY STORAGE AND CONSTRUCTION SHED.
  
 3.3.ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE
 PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE
 STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS.
  
 4) 3309.2 FIRE HAZARDS. THE PROVISIONS OF THIS CODE AND
 THE FLORIDA FIRE PREVENTION CODE SHALL BE STRICTLY
 OBSERVED TO SAFEGUARD AGAINST ALL FIRE HAZARDS
 ATTENDANT UPON CONSTRUCTION OPERATIONS.
  
 5) DURING THE DEMOLITION AS WELL AS THE FONDATION WORK
 A THRESHOLD INSPECTOR SHALL BE ON SITE. THRESHOLD
 INSPECTION PLAN FL S. S. 553.71(7) " THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 6) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A
 SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON
 A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL
 INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE
 STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE
 ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING.
 THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO
 PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO
 THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR
 COMPLIANCE WITH THE PERMITTED DOCUMENTS.
  
 7) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. A THRESHOLD AGREEMENT MUST BE
 SIGNED BY THE THRESHOLD INSPECTOR, CONTRACTOR, OWNERS,
 PLEASE CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 8) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT OR
 ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 9) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 9.1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
 THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN
 CONRAD: [email protected]
  
 9.2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 10) SHEET S.001 STRUCTURAL NOTES 2310 INDICATE A SOILS
 REPORT WAS COMPLETED, FOUNDATION SOILS REPORT HD 135558
 BY DUNKLEBURGER ENGINEERING & TESTING PLEASE PROVIDE
 SOILS REPORT AS REQUIRED BY SECTION 2010 FBC-B 1803.5.2
 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  