Plan Review Notes For Permit 14050703 |
Permit Number |
14050703 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-05-20 14:14:26 | ELECTRICAL PLAN REVIEW DENIED. SEE THE FOLLOWING | | COMMENTS BASED ON THE LATEST EDITION OF THE NFPA 72, | | THE 2008 NEC AND THE 2010 FBC. | | | | 1) PLANS ARE INCOMPLETE. PLEASE INDICATE THE LOCATION | | OF THE FACP ON THE FLOOR PLAN | | | | 2) RISER INDICATES PULL STATIONS. PLEASE INDICATE PULL | | STATIONS ON THE FLOOR PLAN. | | | | 3) NOTIFICATION APPLIANCE CIRCUIT REQUIRED. PLEASE | | INDICATE NOTIFICATION DEVICES ON THE FLOOR PLAN AND | | RISER. | | | | 4) PLEASE PROVIDE AND INDICATE THE REQUIRED VOLTAGE | | DROP AND BATTERY CALCULATIONS FOR THE NEW DEVICES AND | | CIRCUITS. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR AT [email protected] | | | | |
|