2014-05-19 15:29:50 | 2010 FBC | | | | DENIED BY BUILDING | | | | 1) THE STRUCTURE IS LOCATED IN A 170 MPH WIND SPEED, | | THE EXPOSURE CATEGORY IS C, THE MEAN ROOF HEIGHT IS | | LESS THAN 25 FEET AND THE ROOF SLOPE IS 3/12. THE | | MAXIMUM DESIGN PRESSURE FROM THE PRODUCT APPROVAL IS | | TOO LOW FOR THE CORNER AND PERIMETER ROOF AREAS. THE | | REQUIRED UPLIFT IS -68.0 PSF FOR THE PERIMETER AND | | -99.8 PSF FOR THE CORNERS. SUBMIT TWO SETS OF RAS 117 | | CALCULATIONS AS REQUIRED BY NOA NO. 13-0424.14 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] | | | | |
|