Plan Review Notes
Plan Review Notes For Permit 14050698
Permit Number 14050698
Review Stop B
Sequence Number 1
Notes
Date Text
2014-05-19 15:29:502010 FBC
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN A 170 MPH WIND SPEED,
 THE EXPOSURE CATEGORY IS C, THE MEAN ROOF HEIGHT IS
 LESS THAN 25 FEET AND THE ROOF SLOPE IS 3/12. THE
 MAXIMUM DESIGN PRESSURE FROM THE PRODUCT APPROVAL IS
 TOO LOW FOR THE CORNER AND PERIMETER ROOF AREAS. THE
 REQUIRED UPLIFT IS -68.0 PSF FOR THE PERIMETER AND
 -99.8 PSF FOR THE CORNERS. SUBMIT TWO SETS OF RAS 117
 CALCULATIONS AS REQUIRED BY NOA NO. 13-0424.14
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  