Plan Review Notes For Permit 14050582 |
Permit Number |
14050582 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2014-06-11 10:48:26 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | HAVING REVIEWED THE SITE PLAN FOR THE FIRST TIME, THERE | | ARE MULTIPLE TEMPORAY TRAILERS INDICATED IN THE PARKING | | LOT AREA. | | | | THESE TEMPORAY TRAILERS SHALL MEET THE MINIMUM | | SEPARATION DISTANCE REQUIREMENTS OF NFPA 241, CHAPTER | | 4, TABLE 4.2.1. | | | | SEPARATION DISTANCES SHALL BE PROVIDED ON THE SITE | | PLAN. THE TRAILERS SHALL BE SEPARATED ACCORDING TO THE | | INDICATED SEPARATION DISTANCES. | | | | A 75 PERCENT REDUCTION IN SEPARATION DISTANCE SHALL BE | | APPLIED PROVIDED AUTOMATIC SPRINKLER PROTECTION IS USED | | IN THE EXPOSING STRUCTURE. | | | | AS PROPOSED, FIRE SPRINKLER PROTECTION IS REQUIRED IN | | EACH OF THE TRAILERS ON THE SITE PLAN, SPRINKLER | | PROTECTION SHALL BE INDICATED ON THE RESUBMITTED PLAN | | UNDER SEPARATE SHOP DRAWINGS. | | | | ADA COMPLAINT STAIR/RAMP PLANS WERE NOT PROVIDED. |
|