2014-06-15 09:59:52 | ****PROVISO**** |
| ***ISSUED AT CONTRACTOR'S RISK*** |
| ***REVISION REQUIRED PRIOR TO FIRST INSPECTION**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 1. THE ANCHORING SHEET PREPARED BY JOHN A BODZIAK, |
| ARCHITECT, IS A PHOTOCOPY. DOCUMENTS SUBMITTED FOR |
| PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| ORIGINALS. FUTURE SUBMITTALS TO INCLUDE ORIGINAL |
| SIGNATURE. PLEASE HAVE ARCHITECT ACKNOWLEDGE |
| REQUIREMENT; THIS CAN BE DONE EITHER HARD COPY BY MAIL |
| OR VIA EMAIL. NO FURTHER ACTION REQUIRED. |
| |
| 2. IMPACT PROTECTION REQUIRED, SEE SHEET 1, SITE |
| INSTALLED ITEMS. ALSO PLEASE NOTE THAT ON PAGE 1, |
| APPROVED PRODUCTS LIST, THE DOOR (FL14237) STATES THAT |
| SHUTTERS ARE REQUIRED. THIS IS AN IMPACT RATED DOOR PER |
| WWW.FLORIDABUILDING.ORG, SO PLEASE EXCLUDE THIS FROM |
| YOUR SHUTTER PERMIT APPLICATION OR REVISION AS THIS |
| WOULD OBSTRUCT THE EXIT AND IS NOT NECESSARY. SEPARATE |
| PERMIT REQUIRED. |
| |
| 3. SEE FBC TABLE 705.8. DISTANCES BETWEEN BUILDINGS |
| WERE NOT SHOWN ON THE SITE PLAN. REVISE SITE PLAN TO |
| SHOW COMPLIANCE. PLEASE ALSO SEE FBC 705.3, EXCEPTION. |
| |
| 4. SHEET A100, RAMP & DECK PLAN PREPARED BY MODULAR |
| PLANS DESIGN, CO (MDP COMPANY ARCHITECTS), THOMAS L. |
| MELTON (AR0017033) IS LACKING THE ARCHITECT BUSINESS |
| LICENSE NUMBER IN THE TITLE BLOCK (FAC61G15-23.002, FS |
| 481). REVISE THIS SHEET TO INCLUDE THE REQUIRED |
| INFORMATION. IF THIS COMPANY DOES NOT HAVE AN ARCHITECT |
| BUSINESS LICENSE, PROVIDE EVIDENCE THAT THIS HAS BEEN |
| APPLIED FOR (MAY BE SENT VIA EMAIL). |
| |
| |
| |
| 3. WHEN RESUBMITTING, ALWAYS COLLATE SHEETS, FBC 107. |
| |