Date Text
2014-06-15 09:59:52****PROVISO****
 ***ISSUED AT CONTRACTOR'S RISK***
 ***REVISION REQUIRED PRIOR TO FIRST INSPECTION****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE ANCHORING SHEET PREPARED BY JOHN A BODZIAK,
 ARCHITECT, IS A PHOTOCOPY. DOCUMENTS SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS. FUTURE SUBMITTALS TO INCLUDE ORIGINAL
 SIGNATURE. PLEASE HAVE ARCHITECT ACKNOWLEDGE
 REQUIREMENT; THIS CAN BE DONE EITHER HARD COPY BY MAIL
 OR VIA EMAIL. NO FURTHER ACTION REQUIRED.
  
 2. IMPACT PROTECTION REQUIRED, SEE SHEET 1, SITE
 INSTALLED ITEMS. ALSO PLEASE NOTE THAT ON PAGE 1,
 APPROVED PRODUCTS LIST, THE DOOR (FL14237) STATES THAT
 SHUTTERS ARE REQUIRED. THIS IS AN IMPACT RATED DOOR PER
 WWW.FLORIDABUILDING.ORG, SO PLEASE EXCLUDE THIS FROM
 YOUR SHUTTER PERMIT APPLICATION OR REVISION AS THIS
 WOULD OBSTRUCT THE EXIT AND IS NOT NECESSARY. SEPARATE
 PERMIT REQUIRED.
  
 3. SEE FBC TABLE 705.8. DISTANCES BETWEEN BUILDINGS
 WERE NOT SHOWN ON THE SITE PLAN. REVISE SITE PLAN TO
 SHOW COMPLIANCE. PLEASE ALSO SEE FBC 705.3, EXCEPTION.
  
 4. SHEET A100, RAMP & DECK PLAN PREPARED BY MODULAR
 PLANS DESIGN, CO (MDP COMPANY ARCHITECTS), THOMAS L.
 MELTON (AR0017033) IS LACKING THE ARCHITECT BUSINESS
 LICENSE NUMBER IN THE TITLE BLOCK (FAC61G15-23.002, FS
 481). REVISE THIS SHEET TO INCLUDE THE REQUIRED
 INFORMATION. IF THIS COMPANY DOES NOT HAVE AN ARCHITECT
 BUSINESS LICENSE, PROVIDE EVIDENCE THAT THIS HAS BEEN
 APPLIED FOR (MAY BE SENT VIA EMAIL).
  
  
  
 3. WHEN RESUBMITTING, ALWAYS COLLATE SHEETS, FBC 107.
  