2014-06-19 15:57:422010 FBC
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A SURVEY FOR EACH UNIT TO SHOW
 THAT THE PROPERTY HAS BEEN SUB-DIVIDED TO CREATE
 TOWNHOUSES.
  
 2) EACH OF THE NEW TOWNHOUSES ARE REQUIRED TO HAVE
 THEIR OWN STREET ADDRESS. CONTACT SCOTT ALEF AT
 561-494-1094.
  
 3) ONE OF THE APPROVED PLANS WILL HAVE TO BE REVIEWED
 BY PALM BEACH COUNTY TO DETERMINE IF ANY IMPACT FEES
 ARE DUE.
  
 4) THE ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS CAN NOT BE WORSE CASE. THEY ARE REQUIRED
 TO BE SITE SPECIFIC. EACH TOWNHOUSE IS REQUIRED TO HAVE
 ENERGY CALCULATIONS AND EQUIPMENT SIZING CALCULATIONS.
 THE ADDRESS OF EACH UNIT IS REQUIRED ON THE FORM AND
 THE UNIT TYPE (IE. GARAGE RIGHT, GARAGE LEFT, INTERIOR
 UNIT, END UNIT, ETC.). FBC ENERGY CONSERVATION 401.2
  
 5) CORRECT THE WIND DESIGN DATA ON SHEET T-2. THE
 CORRECT WINDSPEED FOR THIS PROJECT IS 170 MPH VULT /
 132 VASD. FBCR 301.2.1
  
 6) PROVIDE ADDITIONAL DETAILS FOR THE STEEL BUCKET
 TRUSS HANGER IN THE CONNECTOR SCHEDULE ON SHEET T-2.
 PROVIDE A SIDE VIEW WITH DIMENSIONS AND SPECIFY THE
 WELD TYPES. CITY AMENDMENTS 107.2.1.3
  
 7) THE ROOF SLOPE IS SPECIFIED AS 5/12 ON SHEET 3 AND
 ON SHEET T-2 AND THE TYPICAL END DETAIL IT IS 4/12.
 PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 8) ON SHEET D1 THE FLOOR TRUSS BEARING LEDGER IS
 SPECIFIED AS (2) 2 X 6S AND ON SHEETS W-1 & T-1 IT IS
 (2) 2 X 12S. PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 9) THE ANCHORS THAT ARE SPECIFIED FOR THE LEDGER ARE
 INCONSISTENT. 1/2", 5/8" & 3/4" DIAMETERS AND 4-1/2" &
 5" EMBED DEPTHS ARE GIVEN. PLEASE CORRECT. CITY
 AMENDMENTS 107.2.1
  
 10) SHOW COMPLIANCE WITH FBCR 302.6 FOR DWELLING /
 GARAGE FIRE SEPARATION REQUIREMENTS FOR MINIMUM 5/8"
 TYPE X DRYWALL ON CEILING.
  
 11) SHOW COMPLIANCE WITH FBCR 302.5.1 AND FBC ENERGY
 CONSERVATION FOR REQUIREMENTS FOR THE DOOR FROM THE
 GARAGE TO THE RESIDENCE.
  
 12) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.3.4.1
  
 13) SUBMIT PRODUCT APPROVALS FOR THE IMPACT RATED
 WINDOWS AND DOORS, STRUCTURAL MULLIONS, SLIDING GLASS
 DOOR, OVERHEAD GARAGE DOOR, ROOF MATERIALS FOR THE FLAT
 ROOF AS REQUIRED BY DCA RULE 9N-3.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714