Date |
Text |
2014-05-20 19:17:39 | PERMITS 14050547, 14050556, 14050561, 14050566 |
| THE ABOVE MENTIONED PERMITS WERE REVIEWED FOR |
| ELECTRICAL COMPLIANCE TODAY. AS A RESULT OF THE REVIEW, |
| THE FOLLOWING COMMENTS WERE GENERATED. SOME ARE UNIT |
| SPECIFIC AND OTHERS PERTAIN TO THE PROJECT AS A WHOLE. |
| 1. YOU SHALL PROVIDE A SITE PLAN INDICATING THE |
| LOCATION OF THE FPL SOURCE OF POWER TO EACH OF THE |
| UNITS. IF ANY OF THE FPL FEEDERS INTERSECT OR CROSS |
| UNDER AN ADJOINING LOT, PROVISIONS FOR A RECORDED |
| EASEMENT SHALL BE ADDRESSED. |
| 2. THE SUBMITTED ELECTRICAL PLANS DO NOT INDICATE THE |
| LOCATION OF THE ELECTRIC METER FOR UNITS 2 & 3. THERE |
| SHALL BE A SERVICE DISCONNECT IN ACCORDANCE WITH NEC |
| 230.70(A)(1). |
| 3. IN ADDITION TO THE ELECTRICAL NOTES ALREADY ON THE |
| PLANS, A NOTE AS TO THE CEILING BOX REQUIREMENT OF NEC |
| 314.27 SHALL BE MADE. |
| 4. AS A SUGGESTION, A 3 WAY SWITCH SHOULD BE ADDED IN |
| THE LIVING ROOM BETWEEN THE ENTRY WAY AND THE STAIRS. |
| 5. BECAUSE THE SUBMITTED PANEL SCHEDULES PROVE TO BE |
| GENERIC AS WELL AS THE LOAD CALCS, I WENT OVER THEM AND |
| THE SERVICE CONDUCTORS AS INDICATED ON THE RISER |
| DIAGRAMS ARE ADEQUATE FOR THE LOAD. |
| I. IN ADDITION TO THE ABOVE MENTIONED, THE ONLY OTHER |
| CORRECTIONS REQUIRED WOULD BE TO BETTER SCRUTINIZE THE |
| LINEAR WALL SPACE FOR COMPLIANCE WITH THE VARIOUS |
| REQUIREMENTS OF NEC 210.52. |
| I HAVE GREEN LINED ONE OF THE SETS WITH THE OUTLET |
| PLACEMENT FOR CODE COMPLIANCE. FEEL FREE TO COME IN TO |
| CHECK OUT THIS SET FOR YOUR CORRECTIONS. |
| THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL |
| PLANS EXAMINER |
| YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE |
| FOLLOWING LINK: |
| |
| HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT |
| US.ASPX |
| |
| ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS |
| EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, |
| AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB |
| ABOVE THE SECOND PERMIT INFORMATION). |
| AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR |
| COMPLIANCE WITH ANY NOTES, PROVISOS, OR OTHER PERMIT |
| CONDITIONS. |
| FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. |