2014-07-22 12:20:53 | BUILDING PLAN REVIEW |
| REVISION: 14050507 |
| PERMIT: 13010504 |
| ADD: 631 EVERNIA ST. |
| CONT: MOSS |
| TEL: (561 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 3RD REVIEW |
| DATE: FRIDAY AUGUST 29/ 2014 |
| ACTION: DENIED |
| |
| NOTICE: NOTE: |
| CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A |
| LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE |
| FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE |
| TIMES FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION. |
| |
| |
| 1) SHEET A-203 NEW RECYCLING ROOM (200G) THE LOCATION |
| OF THE DOOR TO THIS ROOM BLOCKS THE EGRESS IN IT SWING. |
| BECAUSE OF THE DOOR LOCATION THERE IS APPROXIMATLY 17 |
| INCHES CLEAR WHEN THE DOOR IS OPEN AT 90 DEGREES. THE |
| 2010 FBC-B 1008.1.9.11 DURING ITS SWING, ANY DOOR IN A |
| MEANS OF EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE |
| HALF OF THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, |
| PASSAGEWAY, OR LANDING, NOR PROJECT MORE THAN 7 INCHES |
| (178 MM) INTO THE REQUIRED WIDTH OF AN AISLE, CORRIDOR, |
| PASSAGEWAY OR LANDING, WHEN FULLY OPEN. THIS COMMON TO |
| ALL THE RESIDENCE FLOORS. THE DOOR NEEDS TO BE MOVED SO |
| THAT 1/2 OF THE REQUIRED EGRESS (22 INCHES) IS MET, |
| SHOW THE DIMENSION ON THE PLANS. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |