Plan Review Notes
Plan Review Notes For Permit 14050507
Permit Number 14050507
Review Stop B
Sequence Number 2
Notes
Date Text
2014-07-22 12:20:53BUILDING PLAN REVIEW
 REVISION: 14050507
 PERMIT: 13010504
 ADD: 631 EVERNIA ST.
 CONT: MOSS
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRIDAY AUGUST 29/ 2014
 ACTION: DENIED
  
 NOTICE: NOTE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A
 LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE
 FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE
 TIMES FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION.
  
  
 1) SHEET A-203 NEW RECYCLING ROOM (200G) THE LOCATION
 OF THE DOOR TO THIS ROOM BLOCKS THE EGRESS IN IT SWING.
 BECAUSE OF THE DOOR LOCATION THERE IS APPROXIMATLY 17
 INCHES CLEAR WHEN THE DOOR IS OPEN AT 90 DEGREES. THE
 2010 FBC-B 1008.1.9.11 DURING ITS SWING, ANY DOOR IN A
 MEANS OF EGRESS SHALL LEAVE UNOBSTRUCTED AT LEAST ONE
 HALF OF THE REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY, OR LANDING, NOR PROJECT MORE THAN 7 INCHES
 (178 MM) INTO THE REQUIRED WIDTH OF AN AISLE, CORRIDOR,
 PASSAGEWAY OR LANDING, WHEN FULLY OPEN. THIS COMMON TO
 ALL THE RESIDENCE FLOORS. THE DOOR NEEDS TO BE MOVED SO
 THAT 1/2 OF THE REQUIRED EGRESS (22 INCHES) IS MET,
 SHOW THE DIMENSION ON THE PLANS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]