2014-05-22 12:50:56ELECTRICAL PLAN REVIEW HAS BEEN FOUND TO BE DEFICIENT
 IN THE AREAS LISTED BELOW. COMPLIANCE SHALL BE BASED ON
 THE 2008 NEC, THE 2010 FBC, AND THE 2007 NFPA 72
  
 1) SMOKE DETECTORS ARE INDICATED ON THE FLOOR PLAN BUT
 NOT ON THE RISER DIAGRAM. THE SMOKE DETECTORS WILL HAVE
 TO TIE TO THE EXISTING FACP. PLEASE INDICATE WITH A
 LINE DIAGRAM HOW THIS WILL BE ACCOMPLISHED.
  
 2) THE SMOKE DETECTORS SHALL BE COMPATABLE TO THE
 EXISTING FACP. PLEASE INDICATE ON THE PLAN THE
 MANUFACTURER OF THE FACP AND SUBMIT SUPPORTING
 DOCUMENTATION INDICATING COMPATABILITY.