2014-08-19 16:54:54 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) THE PROPOSED WORK IS TO ENCLOSE THE COURTYARD AREA |
| ON THE ZERO LOT LINE SIDE OF THE DWELLING. THE COURT |
| YARD FOR THIS MODEL SERVES AS PART OF THE REQUIRED |
| EMERGENCY ESCAPE AND RESCUE OPENING FOR A SLEEPING |
| ROOM. THE BUILDING CODE DOES NOT ALLOW OPENINGS ON THE |
| ZERO LOT LINE. HAVING THE COURTYARD PROVIDED A WALL |
| THAT WAS NOT ON THE ZERO LOT LINE AND ALLOWED THE |
| REQUIRED EGRESS OPENING FOR THE SLEEPING ROOMS. THE |
| HATCH OPENING IN THE COURTYARD WALL PROVIDES AN ESCAPE |
| ROUTE FROM THE SLEEPING ROOM AND ACCESS TO THE SLEEPING |
| ROOM FOR RESCUE PERSONNEL. THERE IS ALSO AN EMERGENCY |
| EGRESS EASEMENT ACROSS THE ADJACENT PROPERTY IN THE |
| SUBDIVISION COVENANTS. IN ORDER TO BE APPROVED BY THE |
| BUILDING OFFICIAL, THE CLOSET WILL NEED TO BE REMOVED |
| FROM THE "OFFICE" AND THE LABEL "NOT TO BE USED AS A |
| SLEEPING ROOM" ADDED TO THE PLAN BELOW THE ROOM NAME. |
| |
| 2) COMPLIED. |
| |
| 3) COMPLIED. |
| |
| 4) COMPLIED. |
| |
| 5) THE PROPOSED PLAN SPECIFIES A 3' X 3' CASEMENT |
| WINDOW ON THE ZERO LOT LINE. NO OPENINGS ARE ALLOWED ON |
| A ZERO LOT LINE. ONE HOUR FIRE RATED GLASS BLOCK IS |
| ALLOWED. FBCR 302.1 SUBMIT TWO COPIES OF THE PRODUCT |
| APPROVALS FOR THE ONE HOUR FIRE RATED GLASS BLOCK AS |
| REQUIRED BY DCA RULE 9N-3. |
| |
| 6) COMPLIED. |
| |
| 7) COMPLIED. |
| |
| 8) COMPLIED. |
| |
| 9) COMPLIED. |
| |
| 10) COMPLIED. |
| |
| 11) THE ROOF SHEATHING FASTENING IS INCONSISTENT. 10D |
| NAILS ARE SPECIFIED IN DETAIL 3 ON S-2 AND 8D NAILS ARE |
| SPECIFIED ALSO. PLEASE CORRECT. CITY AMENDMENTS 107.2.1 |
| AND FBC R803.2.3.1 CHECK ALL OF THE ROOF SHEATHING |
| FASTENING NOTES AND CORRECT THEM OR REMOVE SOME OF THEM |
| SO THAT THEY ARE CONSISTENT. |
| |
| 12) COMPLIED. |
| |
| 13) ON SHEET S-2, HETA-16 EMBED TYPE TRUSS ANCHORS ARE |
| SPECIFIED AT THE EXISTING WALL FOR THE 2 X 8 ROOF |
| JOISTS. A DOUBLE 2 X 8 LEDGER IS ALSO SPECIFIED AT THIS |
| LOCATION. THIS DOES NOT APPEAR TO BE THE CORRECT ANCHOR |
| FOR THIS LOCATION. PLEASE CLARIFY. PROVIDE A STRUCTURAL |
| SECTION DETAIL OF THIS LOCATION. THE HETA-16 EMBED TYPE |
| TRUSS ANCHORS CAN NOT BE USED WITH CONCRETE SCREWS. |
| SPECIFY ANOTHER TYPE OF CONNECTOR SUCH AS AN MTSM 16 |
| WHICH USES TITEN CONCRETE SCREWS FOR FASTENING TO |
| CONCRETE OR CMU. |
| |
| 14) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE |
| SPRAY FOAM INSULATION. FBC R316.3 AND R316.4 THE |
| CEILING INSULATION WAS CHANGED TO R-30 BATTS. THE R30 |
| BATTS ARE 9.5 INCHES THICK AND WILL NOT FIT INTO A 2 X |
| 8 SINGLE ASSEMBLY ROOF/CEILING. INSULATION LOSES |
| R-VALUE WHEN IT IS COMPRESSED AND IN ADDITION TO THE |
| INSULATION, A MINIMUM ONE INCH AIR SPACE IS REQUIRED TO |
| PROVIDE FOR ROOF VENTILATION FBCR 806.3. A CONTINOUS |
| EAVE VENT WILL BE REQUIRED TO VENT THE SINGLE ASSEMBLY |
| ROOF/CEILING. FBCR 806.1 |
| |
| 15) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| PRODUCTS REGULATED BY DCA RULE 9N-3, SUCH AS, ROOF |
| COVERING, TRUSS ANCHORS, GLASS BLOCK. THE PRODUCT |
| APPROVALS ARE REQUIRED TO BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD. CITY AMENDMENTS |
| 107.3.4.1 |
| |
| 16) COMPLIED. |
| |