Plan Review Notes
Plan Review Notes For Permit 14050415
Permit Number 14050415
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-07 08:15:092010 FBC
  
 DENIED BY BUILDING
  
 1) THE PROPOSED WORK IS TO ENCLOSE THE COURTYARD AREA
 ON THE ZERO LOT LINE SIDE OF THE DWELLING. THE COURT
 YARD FOR THIS MODEL SERVES AS PART OF THE REQUIRED
 EMERGENCY ESCAPE AND RESCUE OPENING FOR A SLEEPING
 ROOM. THE BUILDING CODE DOES NOT ALLOW OPENINGS ON THE
 ZERO LOT LINE. HAVING THE COURTYARD PROVIDED A WALL
 THAT WAS NOT ON THE ZERO LOT LINE AND ALLOWED THE
 REQUIRED EGRESS OPENING FOR THE SLEEPING ROOMS. THE
 HATCH OPENING IN THE COURTYARD WALL PROVIDES AN ESCAPE
 ROUTE FROM THE SLEEPING ROOM AND ACCESS TO THE SLEEPING
 ROOM FOR RESCUE PERSONNEL. THERE IS ALSO AN EMERGENCY
 EGRESS EASEMENT ACROSS THE ADJACENT PROPERTY IN THE
 SUBDIVISION COVENANTS.
 THE BUILDING OFFICIAL WILL DETERMINE IF THE PROPOSED
 WORK CAN BE ALLOWED. PLEASE SUBMIT TWO SETS OF FLOOR
 PLANS FOR THE ENTIRE DWELLING WITH ALL OF THE EXISTING
 ROOMS LABELED. SHOW THE LOCATIONS OF THE CLOSETS, DOORS
 AND WINDOWS. FBC R310
  
 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE
 ADDITION. FBC ENERGY CONSERVATION 401.2
  
 3) THE CONSTRUCTION TYPE IS INCORRECTLY SPECIFIED AS
 III-B ON SHEET CVR. THE CONSTRUCTION TYPE FOR THIS
 STRUCTURE IS V-B. FBC 602
  
 4) THE OCCUPANCY TYPE IS INCORRECTLY SPECIFIED AS R1A
 ON SHEET CVR. THE OCCUPANCY TYPE FOR THIS SINGLE FAMILY
 DWELLING IS R-3 .
  
 5) THE PROPOSED PLAN SPECIFIES A 3' X 3' CASEMENT
 WINDOW ON THE ZERO LOT LINE. NO OPENINGS ARE ALLOWED ON
 A ZERO LOT LINE. ONE HOUR FIRE RATED GLASS BLOCK IS
 ALLOWED. FBCR 302.1
  
 6) THE EXISTING FOOTING WAS DESIGNED TO SUPPORT A CBS
 WALL, IF YOU INTEND TO USE IT TO SUPPORT AN EXTERIOR
 BEARING WALL, THE FOOTER AND EXISTING WALL WILL NEED TO
 BE EVALUATED FOR ALL OF THE REQUIRED LOADS OR A COPY OF
 THE ORIGINAL PLANS FOR THE WALL WILL NEED TO BE
 SUBMITTED. FBC R401.2 THE DEMO PLAN ON SHEET D-1 AND
 WALL SECTION 7 ON A-1 SHOW THAT THE EXISTING FOOTER,
 WALL AND SLAB ARE TO BE USED.
  
 7) SHEET S-1 APPEARS TO SHOW THAT A NEW FOOTING, WALL
 AND SLAB WILL BE CONSTRUCTED. PLEASE CLARIFY. CITY
 AMENDMENTS 107.2.1
  
 8) SHOW COMPLIANCE WITH FBC R318 FOR TERMITE
 PROTECTION, IF THE EXISTING SLAB IS USED.
  
 9) SHOW COMPLIANCE WITH FBC R506.2.3 FOR THE REQUIRED
 UNDER SLAB VAPOR RETARDER, IF THE EXISTING SLAB IS
 USED.
  
 10) SHOW COMPLIANCE WITH FBC R404.1.6 FOR THE REQUIRED
 HEIGHT ABOVE GRADE, IF THE EXISTING SLAB IS USED.
  
 11) THE ROOF SHEATHING FASTENING IS INCONSISTENT. 10D
 NAILS ARE SPECIFIED IN DETAIL 3 ON S-2 AND 8D NAILS ARE
 SPECIFIED ALSO. PLEASE CORRECT. CITY AMENDMENTS 107.2.1
 AND FBC R803.2.3.1
  
 12) THE SINGLE ASSEMBLE ROOF RAFTERS/JOISTS ARE
 SPECIFIED AS 2 X 6 ON SECTION 7/A-1 AND 2 X 8 ON S-2.
 PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 13) ON SHEET S-2, HETA-16 EMBED TYPE TRUSS ANCHORS ARE
 SPECIFIED AT THE EXISTING WALL FOR THE 2 X 8 ROOF
 JOISTS. A DOUBLE 2 X 8 LEDGER IS ALSO SPECIFIED AT THIS
 LOCATION. THIS DOES NOT APPEAR TO BE THE CORRECT ANCHOR
 FOR THIS LOCATION. PLEASE CLARIFY. PROVIDE A STRUCTURAL
 SECTION DETAIL OF THIS LOCATION.
  
 14) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 SPRAY FOAM INSULATION. FBC R316.3 AND R316.4
  
 15) SUBMIT PRODUCT APPROVALS FOR THE PRODUCTS REGULATED
 BY DCA RULE 9N-3, SUCH AS, ROOF COVERING, TRUSS
 ANCHORS, GLASS BLOCK.
  
 16) THE VALUE OF $11,500.00 IS LOW FOR THIS SCOPE WORK.
 FOR PERMITTING PURPOSES VALUATION SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, OVERHEAD AND
 PROFIT. PLEASE SUBMIT A COPY OF THE SIGNED CONTRACT.
 CITY AMENDMENTS 109.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]