2014-05-19 10:16:18ELECTRIC REVIEW DENIED. ALL DEFICIENCIES BASED ON THE
 2010 FBC AND THE 2008 NEC.
  
 1) ADDITIONAL RECEPTACLES MAY BE REQUIRED IN THE LIVING
 ROOM. ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE
 THAN 6 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE
 THAN 2 FEET IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
 2) THE RISER DIAGRAM INDICATES A NEW 200AMP MAIN PANEL
 INSIDE THE RESIDENCE WITH NO MAIN DISCONNECT INDICATED
 NEXT TO THE METER OUTSIDE. THE SERVICE ENTRANCE
 DISCONNECTING MEANS SHALL BE INSTALLED TO COMPLY WITH
 NEC 230.70.
  
 3) PLEASE PROVIDE THE PANEL SCHEDULES AND SHOW CIRCUITS
 ON FLOOR PLAN. FBC- 107.3.5.3
  
 4) A BONDING STRIP IS REQUIRED AT SERVICE GROUND NEC
 250.94
  
 5) PROVIDE A GROUNDING ELECTRODE FOR THE GUEST HOUSE
 ELECTRIC PANEL AND INDICATE IT ON THE PLANS. NEC 250.32
  
 6) LUMINAIRES IN CLOTHES CLOSETS. ARTICLE 410.16 (C)(3)
 LOCATION. STATES IN PART , THE MINIMUM CLEARANCE
 BETWEEN LUMINAIRES INSTALLED IN CLOTHES CLOSETS AND THE
 NEAREST POINT OF A STORAGE SPACE SHALL BE AS FOLLOWS:
 "150MM (6") FOR RECESSED INCANDESCENT OR LED LUMINAIRES
 WITH A COMPLETELY ENCLOSED LIGHT SOURCE INSTALLED IN
 THE WALL OR CEILING" OR (4) "150MM (6") FOR RECESSED
 FLUORESCENT LUMINAIRES INSTALLED IN THE WALL OR
 CEILING." PLEASE INDICATE COMPLIANCE WITH THIS SECTION
 OF THE NEC WHERE INSTALLING RECESSED LIGHTING IN THE
 CLOTHES CLOSET IN THE MASTER BEDROOM.
  
 7) BATHROOM GFIC OUTLET. BATHROOM BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, AT LEAST ONE 20-AMPERE
 BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM
 RECEPTACLE OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS. THE PLAN SHOWS NEW OUTLET IN THE BATHROOM FOR
 A LIGHTED MIRROR. PLEASE INDICATE COMPLIANCE WITH
 ARTICLE 210.11 (C)(3)
  
 8) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2010 FBC R314, 315
  
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]