Plan Review Notes For Permit 14050335 |
Permit Number |
14050335 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-06-07 12:37:46 | 2010 FBC | | | | PLUMBING DENIED | | | | 1) SPECIFY THE DRAIN AND VENT PIPE SIZES ON THE RISER | | DIAGRAM. FBCR P3005.4 AND P3113.1 | | | | 2) SHOW COMPLIANCE WITH FBCR P3101.2 AND P3101.2 FOR | | TRAP SEAL PROTECTION AND APPROVED VENTING METHODS. | | THERE ARE SEVERAL FIXTURES THAT ARE NOT PROPERLY VENTED | | ON BOTH FLOORS. | | | | 3) THE SECOND FLOOR RISER IS MIS-LABELED AS THE FIRST | | FLOOR RISER. PLEASE CORRECT. CITY AMENDMENTS 107.2.1 | | | | 4) SHOW WHERE THE SECOND FLOOR BUILDING DRAINS TIE INTO | | THE FIRST FLOOR BUILDING DRAIN. FOR CLARITY, PROVIDE | | THE PLUMBING RISER DIAGRAM AS A WHOLE SYSTEM RATHER | | THAN THREE SEPARATE PARTS. CITY AMENDMENTS 107.2.1 | | | | 5) A FLOOR DRAIN IS REQUIRED FOR THE ICE MACHINE IN THE | | KITCHEN. FBCR P2719 | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|