Plan Review Notes
Plan Review Notes For Permit 14050335
Permit Number 14050335
Review Stop P
Sequence Number 1
Notes
Date Text
2014-06-07 12:37:462010 FBC
  
 PLUMBING DENIED
  
 1) SPECIFY THE DRAIN AND VENT PIPE SIZES ON THE RISER
 DIAGRAM. FBCR P3005.4 AND P3113.1
  
 2) SHOW COMPLIANCE WITH FBCR P3101.2 AND P3101.2 FOR
 TRAP SEAL PROTECTION AND APPROVED VENTING METHODS.
 THERE ARE SEVERAL FIXTURES THAT ARE NOT PROPERLY VENTED
 ON BOTH FLOORS.
  
 3) THE SECOND FLOOR RISER IS MIS-LABELED AS THE FIRST
 FLOOR RISER. PLEASE CORRECT. CITY AMENDMENTS 107.2.1
  
 4) SHOW WHERE THE SECOND FLOOR BUILDING DRAINS TIE INTO
 THE FIRST FLOOR BUILDING DRAIN. FOR CLARITY, PROVIDE
 THE PLUMBING RISER DIAGRAM AS A WHOLE SYSTEM RATHER
 THAN THREE SEPARATE PARTS. CITY AMENDMENTS 107.2.1
  
 5) A FLOOR DRAIN IS REQUIRED FOR THE ICE MACHINE IN THE
 KITCHEN. FBCR P2719
  