2014-06-07 12:02:41 | 2010 FBC |
| |
| DENIED BY BUILDING |
| |
| 1) THE PROPOSED STRUCTURE IS LOCATED IN A SPECIAL FLOOD |
| HAZARD ZONE A5 WITH A 7' BFE. THE CITY OF WEST PALM |
| BEACH'S FLOOD ORDINANCE REQUIRES NEW CONSTRUCTION TO |
| HAVE A FINISH FLOOR ELEVATION OF 7.5' NGVD ( WHICH |
| INCLUDES A SIX INCH FREEBOARD ). AN ELEVATION |
| CERTIFICATE IS REQUIRED FOR THE PROPOSED GARAGE AND |
| EQUIPMENT. SPECIFY THE PROPOSED FINISH FLOOR ELEVATIONS |
| ON THE PLANS IN FEET N.G.V.D. |
| TWO COPIES OF A BROCHURE FOR SMART VENT FLOOD VENTS |
| WERE IN THE PAPER WORK THAT WAS SUBMITTED. IF THE |
| INTENT IS TO CONSTRUCT THE GARAGE WITH A FINISH FLOOR |
| BELOW THE REQUIRED BASE FLOOD ELEVATION, THE PLANS ARE |
| REQUIRED TO SHOW COMPLIANCE WITH FEMA REQUIREMENTS. THE |
| ENCLOSED GARAGE CAN ONLY BE USED FOR THE PARKING OF |
| VEHICLES. APPLIANCES, HEATING AND COOLING EQUIPMENT, |
| PLUMBING FIXTURES, ELECTRICAL EQUIPMENT ( OTHER THAN |
| THE MINIMUM REQUIRED FOR LIFE SAFETY AND ELECTRIC CODE |
| REQUIREMENTS FOR BUILDING ACCESS AND STORAGE AREAS ) |
| AND MATERIALS THAT ARE NOT FLOOD DAMAGE-RESISTANT ARE |
| NOT ALLOWED BELOW BFE. SHOW THE LOCATIONS AND NUMBER OF |
| VENT OPENINGS ON THE PLANS. ONLY THE AREA OF THE VENT |
| OPENINGS THAT ARE BELOW THE BFE CAN BE COUNTED TOWARD |
| THE REQUIRED AMOUNT OF FLOOD VENT OPENING AREA. FBC |
| R322 SEE ALSO FEMA PUBLICATION TECHNICAL BULLETIN 1 / |
| AUGUST 2008 FOR ADDITIONAL INFORMATION. |
| |
| 2) THE STRUCTURE IS LOCATED IN AN AREA OF QUESTIONABLE |
| SOIL. SUBMIT TWO SETS OF A SIGNED AND SEALED SUB |
| SURFACE SOIL REPORT. FBC R401.4 |
| |
| 3) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| SMART VENT ENGINEERED FLOOD VENTS (FL #5822.3) WITH |
| INSTALLATION INSTRUCTIONS AS REQUIRED BY DCA RULE 9N-3. |
| |
| 4) SEPARATE PERMITS ARE REQUIRED FOR THE GENERATOR, |
| POOL, POOL DECK AND POOL EQUIPMENT. IF THESE ITEMS WERE |
| INCLUDED IN THE VALUE OF $525,000.00, PLEASE REMOVE |
| THEIR COSTS AND ADJUST THE VALUE ACCORDINGLY. |
| |
| 5) SUBMIT TWO COPIES OF THE ICC-ES EVALUATION REPORTS |
| FOR THE ICYENE SPRAY FOAM INSULATION. FBC R316 |
| |
| 6) PROVIDE A WINDOW AND DOOR BUCK DETAIL THAT SPECIFIES |
| HOW THE BUCKS WILL BE ANCHORED TO THE SUBSTRATE. CITY |
| AMENDMENTS R107.2.1.3 |
| |
| 7) ON SHEET S1.00, GENERAL NOTE 3E COMPONENT AND |
| CLADDING PRESSURES ARE + 48.16 PSF AND - 62.93 PSF. THE |
| WINDOW AND DOOR SCHEDULE HAS +50.43 AND - 67.48 FOR TEN |
| SQFT IN WALL ZONE 5 (EDGES). PLEASE CORRECT. FBC |
| R301.2.1 |
| |
| 8) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR |
| THE CHIMNEY FRAMING TO THE TRUSSES. FBC R301.1 |
| |
| 9) SUBMIT TWO SET OF MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE PREFAB FIREPLACE. FBC |
| R1005 |
| |
| 10) SUBMIT DETAILED DRAWINGS FOR THE MASONRY FIREPLACE |
| AND CHIMNEY SHOWING COMPLIANCE WITH FBC R1001. |
| |
| 11) SPECIFY HOW THE EXTERIOR BALCONY FLOORS WILL BE |
| WATERPROOFED. FBC R903 |
| |
| 12) PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 ARE |
| REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD. CITY AMENDMENTS 107.3.4.1 |
| |
| 13) THE MAXIMUM FRAME SIZE HEIGHT ON THE DOOR PRODUCT |
| APPROVAL FL-10975.6 IS 82" AND ALL OF THE DOORS SHOWN |
| ON THE PLANS ARE 96" IN HEIGHT. PLEASE CORRECT. |
| |
| 14) THE WIDTH OF THE FRONT ENTRY DOOR IS 42" ON THE |
| PLANS AND THE MAXIMUM WIDTH LISTED IN THE NOA NO. |
| 11-1013.24 IS 37". SUBMIT PRODUCT APPROVALS FOR THIS |
| DOOR AS REQUIRED BY DCA RULE 9N-3. |
| |
| 15) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE 4' |
| 8" X 4' 8" AND THE 3' X 4' FIXED GLASS WINDOWS LOCATED |
| IN THE MASTER BATHROOM AND LAUNDRY ROOMS AS REQUIRED BY |
| DCA RULE 9N-3. |
| |
| 16) SPECIFY WHICH ONE OF THE APPROVED SYSTEMS LISTED IN |
| THE PRODUCT APPROVAL (NOA NO. 12-0406.07) FOR THE TAMKO |
| UNDERLAYMENT WILL BE INSTALLED. |
| |
| 17) SHOW COMPLIANCE WITH FBCR 302.12 FOR DRAFTSTOPPING |
| IN THE CONCEALED SPACE OF THE FLOOR/CEILING ASSEMBLY, |
| SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED |
| 1,000 SQUARE FEET. |
| |
| 18) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| A RESPONSE LETTER INDICATING HOW EACH ONE OF THE REVIEW |
| COMMENTS HAS BEEN ADDRESSED. |
| |