Plan Review Notes
Plan Review Notes For Permit 14050331
Permit Number 14050331
Review Stop E
Sequence Number 2
Notes
Date Text
2014-07-01 11:50:28DATE: 7/1/2014
 PROJECT: CHURCHILL RESIDENCE
 PERMIT#: 14050331
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) 250.68 THE CONNECTION OF A GROUNDING ELECTRODE
 CONDUCTOR AT EACH BUILDING OR STRUCTURE WHERE SUPPLIED
 BY A FEEDER(S) OR BRANCH CIRCUIT(S), SHALL BE MADE AS
 SPECIFIED IN THE 2008 EDITION OF THE NEC ARTICLE
 250.68(A) AND (B).
  
 2) PROVIDE AND ILLUSTRATE THE SAFE WORKING CLEARANCES
 AND DEDICATED WORKING SPACE AND ILLUMINATION AT A/C
 DISCONNECTS. NEC 110.26,
  
 3) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8)
 SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION
 FOR PERSONNEL. NEC 210.8. ALL OUTLETS IN THE GARAGE
 SHALL BE GFCI PROTECTED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR AT [email protected]