2014-07-01 11:50:28 | DATE: 7/1/2014 | | PROJECT: CHURCHILL RESIDENCE | | PERMIT#: 14050331 | | CODE: 2008 EDITION OF THE NEC | | 2010 EDITION OF THE FBC | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: PROVISO | | | | 1) 250.68 THE CONNECTION OF A GROUNDING ELECTRODE | | CONDUCTOR AT EACH BUILDING OR STRUCTURE WHERE SUPPLIED | | BY A FEEDER(S) OR BRANCH CIRCUIT(S), SHALL BE MADE AS | | SPECIFIED IN THE 2008 EDITION OF THE NEC ARTICLE | | 250.68(A) AND (B). | | | | 2) PROVIDE AND ILLUSTRATE THE SAFE WORKING CLEARANCES | | AND DEDICATED WORKING SPACE AND ILLUMINATION AT A/C | | DISCONNECTS. NEC 110.26, | | | | 3) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES | | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) | | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION | | FOR PERSONNEL. NEC 210.8. ALL OUTLETS IN THE GARAGE | | SHALL BE GFCI PROTECTED. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR AT [email protected] |
|