2014-09-15 16:31:14****CORRECTIONS****
 ****THIS IS A "FAILED" PLAN REVIEW - "N" ENTERED TO
 ALLOW PERMIT CARD TO PRINT****
 ELEVATION CERTIFICATE FOR 14060942 AND 14050331,
 PREPARED BY ROBERT J. CAJAL, WALLACE SURVEYING CORP
 DATED 12/26/13
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 PROPERTY IS NOW OWNED BY 101 CHURCHILL ROAD LLC. AS
 DISCUSSED, PLEASE HAVE A CONTRACTOR APPLY FOR ALL OPEN
 PERMITS WHICH WERE OBTAINED UNDER THE FLORIDA STATUTE
 489 OWNER BUILDER EXEMPTION. SEE ATTORNEY GENERAL
 OPINION AGO 91-05.
  
 PRIOR TO FORM BOARD INSPECTION ("BUILDING UNDER
 CONSTRUCTION"), PLEASE CORRECT THE FOLLOWING ITEMS ON
 THE ELEVATION CERTIFICATE TO AVOID FIELD DELAYS:
  
 1. A1, A2, A3, IT IS MY UNDERSTANDING THAT THIS PARCEL
 IS UNDERGOING A REPLAT. REVISE THE INFORMATION IN THESE
 FIELDS IF APPLICABLE.
  
 2. A5, LATITUDE/LONGITUDE DOES NOT APPEAR TO BE
 CORRECT. THIS IS TO BE ACCURATE WITHIN 66' OF THE
 CENTER OF THE FRONT OF THE BUILDING.
  
 3. A8C, PLEASE PROVIDE CLARIFICATION ABOUT THE NATURE
 OF THE FLOOD VENTS AND PROVIDE CALCULATIONS OR
 INFORMATION AS TO HOW NET OPENINGS HAS BEEN DETERMINED.
 IN THE PHOTOGRAPH, THE VENT APPEARS BLOCKED. YOU MAY
 FIND THE FOLLOWING DOCUMENT HELPFUL:
  
 TECHNICAL BULLETIN 1, OPENINGS IN FOUNDATIN WALLS AND
 WALLS OF ENCLOSURES (2008)
 HTTP://WWW.FEMA.GOV/MEDIA-LIBRARY/ASSETS/DOCUMENTS/2644
  
 VENTS ARE TO BE INSTALLED WITHIN 1' OF ADJACENT GRADE.
 PLEASE VERIFY WITH PHOTOGRAPHS. ONLY THE PORTION OF THE
 VENT WHICH IS BELOW THE BFE IS TO BE INCLUDED IN THE
 NET OPENING AREA. SEE PAGE 19 OF THE TECHNICAL
 BULLETIN; VENTS THAT CAN BE CLOSED MANUALLY OR THAT
 HAVE COVERS ARE NOT ACCEPTABLE AS FLOOD VENTS.
  
 4. B1, NFIP COMMUNITY NAME IS "CITY OF WEST PALM BEACH"
 (REMOVE "UNINCORPORATED").
  
 5. B6, FIRM INDEX DATE SHOULD BE 03/01/1979.
  
 6. C2E, AS ADVISED DURING PLAN REVIEW, MINIMUM
 ELEVATION FOR ALL EQUIPMENT SERVICING THE BUILDING IS
 7.5'. THE EQUIPMENT WHICH IS CURRENTLY 7.1' WILL BE
 REQUIRED TO BE RAISED PRIOR TO FINAL INSPECTION. IF IT
 IS NOT RAISED PRIOR TO FORM BOARD SURVEY/BUILDING UNDER
 CONSTRUCTION ELEVATION CERTIFICATE, THIS WILL BE A
 PROVISO ITEM AT THAT TIME BUT WILL BE REQUIRED FOR
 "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE.
  
 7. PAGE 2, BUILDING STREET ADDRESS, PLEASE REVISE IF
 ADDRESS OF STRUCTURE HAS CHANGED.
  
  
  
  
  
  
  