2014-05-12 17:59:51FAILED FIRST ELECTRICAL REVIEW AS FOLLOWS:
  
 FROM THE SUBMITTED ELECTRICAL PLAN & RISER I CAN'T
 ASCERTAIN COMPLIANCE WITH NEC 230.2 LIMITING THE BLDG
 TO A SINGLE SERVICE.
  
 IF IT IS THE INTENTION OF THIS WORK TO CONSOLIDATE THE
 EXISTING SERVICE WITH THE NEW ONE, PLEASE INDICATE THIS
 ON THE DRAWINGS. IF IT IS NOT THE INTENTION, AS PER NEC
 230.2(D), THEN COMPLIANCE W/NEC 230.2(E) SHALL BE
 REQUIRED
  
 WHEN ADDRESSING THE ABOVE, COMPLETE NOTE #26 TO COMPLY
 WITH NEC 210.4, AND COMPLETE NOTE #33 TO COMPLY WITH
 NEC 406.8
  