Plan Review Notes For Permit 14050320 |
Permit Number |
14050320 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2014-05-12 17:59:51 | FAILED FIRST ELECTRICAL REVIEW AS FOLLOWS: | | | | FROM THE SUBMITTED ELECTRICAL PLAN & RISER I CAN'T | | ASCERTAIN COMPLIANCE WITH NEC 230.2 LIMITING THE BLDG | | TO A SINGLE SERVICE. | | | | IF IT IS THE INTENTION OF THIS WORK TO CONSOLIDATE THE | | EXISTING SERVICE WITH THE NEW ONE, PLEASE INDICATE THIS | | ON THE DRAWINGS. IF IT IS NOT THE INTENTION, AS PER NEC | | 230.2(D), THEN COMPLIANCE W/NEC 230.2(E) SHALL BE | | REQUIRED | | | | WHEN ADDRESSING THE ABOVE, COMPLETE NOTE #26 TO COMPLY | | WITH NEC 210.4, AND COMPLETE NOTE #33 TO COMPLY WITH | | NEC 406.8 | | | | IF YOU HAVE ANY QUESTIONS ON THIS REVIEW, PLEASE | | CONTACT MIKE ALBARRAN (561) 805-6718 |
|